Inspections for the day of: Tuesday, March 17, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-01285 FIRE-Final Inspection3/17/20153/17/20153/19/2015 2:01:40 PMPPEND
Final pending project related fire sprinkler permit work.
FIR15-00098 INSP-Final Inspection3/17/20153/17/20153/19/2015 2:00:27 PMPPART
Final pending current annual inspection, need to verify appropriate temp head in the vicinity of the unit heater at the new addition.
BLD15-00197 FIRE-Final Inspection3/17/20153/17/20153/17/2015 9:16:11 PMPPASS
Fire life safety approved pending a current certification tag is provided for the existing fire extinguisher as discussed with contractor on site.
FIR15-00068 INSP-Sprinkler Rough-in/Hydro3/16/20153/17/20153/17/2015 9:13:39 PMPPART
Overhead hydrostatic test of the system addition completed satisfactory.
FIR15-00039 INSP-Sprinkler Rough-in/Hydro3/16/20153/17/20153/17/2015 9:11:11 PMPCANC
Overbooked
FIR15-00125 INSP-Sprinkler Rough-in3/16/20153/17/20153/17/2015 9:10:23 PMAFAIL
Items noted include; mixed temp heads, plans indicate 200 deg. heads to be installed, overspaced coverage, field work completed exceeds scope of permit work shown on approved plans- additional heads have been added, coverage below stairs provided and a new riser manifold with control valves added. Need to resubmit plans matching work completed.
FIR14-00482 INSP-Final Inspection3/17/20153/17/20153/17/2015 9:03:12 PMAPASS
Fire alarm permit work passed inspection. Permit finaled.
BLD15-00522 FIRE-Final Inspection3/16/20153/17/20153/17/2015 8:56:31 PMAPASS
Fire life safety inspection completed acceptable.
FIR14-00815 INSP-Sprinkler Rough-in3/13/20153/17/20153/17/2015 8:54:54 PMAPART
Overhead rough-in inspection completed at living units 3rd floor area 3- refer to dated annotations on approved plans. Need corrections at unit 317, 320, 325, 327, and utility room 364- including missing heads, obstructed coverage, provide ssu at utility room, 2" CPVC main at unit 327 mechanical closet must meet listing criteria for the installation if intended to remain exposed.
BLD15-00480 FIRE-Conference3/16/20153/17/20153/17/2015 8:24:28 PMADONE
Regarding project schedule.
FIR15-00051 INSP-Sprinkler Rough-in3/16/20153/17/20153/17/2015 8:23:40 PMAPART
Overhead work approved for cover at the grid ceiling areas.
FIR14-00943 INSP-Final Inspection3/17/20153/17/20153/17/2015 8:22:00 PMAPASS
Inspection passed. Fire alarm permit finaled.
FIR14-00482 INSP-Final Inspection3/17/20153/17/20153/17/2015 8:07:48 AMPCANC
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton Inspection cancelled from web by: Jeff Walton
FIR14-00886 INSP-Final Inspection3/17/20153/17/20153/17/2015 12:00:00 AMPCANC
Overbooked - Meet in the B.25 plan review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler