BLD14-01285
| FIRE-Final Inspection | 3/17/2015 | 3/17/2015 | 3/19/2015 2:01:40 PM | P | PEND |
|
|
Final pending project related fire sprinkler permit work.
|
FIR15-00098
| INSP-Final Inspection | 3/17/2015 | 3/17/2015 | 3/19/2015 2:00:27 PM | P | PART |
|
|
Final pending current annual inspection, need to verify appropriate temp head in the vicinity of the unit heater at the new addition.
|
BLD15-00197
| FIRE-Final Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 9:16:11 PM | P | PASS |
|
|
Fire life safety approved pending a current certification tag is provided for the existing fire extinguisher as discussed with contractor on site.
|
FIR15-00068
| INSP-Sprinkler Rough-in/Hydro | 3/16/2015 | 3/17/2015 | 3/17/2015 9:13:39 PM | P | PART |
|
|
Overhead hydrostatic test of the system addition completed satisfactory.
|
FIR15-00039
| INSP-Sprinkler Rough-in/Hydro | 3/16/2015 | 3/17/2015 | 3/17/2015 9:11:11 PM | P | CANC |
|
|
Overbooked
|
FIR15-00125
| INSP-Sprinkler Rough-in | 3/16/2015 | 3/17/2015 | 3/17/2015 9:10:23 PM | A | FAIL |
|
|
Items noted include; mixed temp heads, plans indicate 200 deg. heads to be installed, overspaced coverage, field work completed exceeds scope of permit work shown on approved plans- additional heads have been added, coverage below stairs provided and a new riser manifold with control valves added. Need to resubmit plans matching work completed.
|
FIR14-00482
| INSP-Final Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 9:03:12 PM | A | PASS |
|
|
Fire alarm permit work passed inspection. Permit finaled.
|
BLD15-00522
| FIRE-Final Inspection | 3/16/2015 | 3/17/2015 | 3/17/2015 8:56:31 PM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 3/13/2015 | 3/17/2015 | 3/17/2015 8:54:54 PM | A | PART |
|
|
Overhead rough-in inspection completed at living units 3rd floor area 3- refer to dated annotations on approved plans. Need corrections at unit 317, 320, 325, 327, and utility room 364- including missing heads, obstructed coverage, provide ssu at utility room, 2" CPVC main at unit 327 mechanical closet must meet listing criteria for the installation if intended to remain exposed.
|
BLD15-00480
| FIRE-Conference | 3/16/2015 | 3/17/2015 | 3/17/2015 8:24:28 PM | A | DONE |
|
|
Regarding project schedule.
|
FIR15-00051
| INSP-Sprinkler Rough-in | 3/16/2015 | 3/17/2015 | 3/17/2015 8:23:40 PM | A | PART |
|
|
Overhead work approved for cover at the grid ceiling areas.
|
FIR14-00943
| INSP-Final Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 8:22:00 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR14-00482
| INSP-Final Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 8:07:48 AM | P | CANC |
|
|
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton Inspection cancelled from web by: Jeff Walton
|
FIR14-00886
| INSP-Final Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 12:00:00 AM | P | CANC |
|
|
Overbooked - Meet in the B.25 plan review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler
|