Inspections for the day of: Tuesday, March 17, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02629 Final3/17/20153/17/20153/19/2015 11:20:13 AMPFAIL
Jon Fivecoat is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce NEC 110.3(B) Installation, Generator not installed with proper air flow clearances as per manufactures requirements
ELE14-03058 Final3/17/20153/17/20153/17/2015 4:32:28 PMPFAIL
Jay Phone #: ###-#### NEC 210.8 receptacle layout for kitchen counter top, Disconnecting means for detacted garage
ELE15-00108 Final3/17/20153/17/20153/17/2015 3:14:16 PMPFAIL
Kara Phone #: ###-#### Habitable living areas shall comply with article 210.8 of the NEC for receptacle spacing.
ELE15-00622 Temporary Service3/17/20153/17/20153/17/2015 1:49:38 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov t/s u/g n ok