Inspections for the day of: Tuesday, March 18, 1997.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE96-04144 INSP - Final3/17/19973/18/19973/18/1997 12:00:00 AMAPASS
03/18/97 403 -
ELE97-00278 INSP - Permanent service3/18/19973/18/19973/18/1997 12:00:00 AMAFAIL
NEC: 384-4. NO PIPING, DUCT WORK,ETC., FOREIGN TO SERVICE EQUIPTMENT SHALL BE INSTALLED. NEC: 110-16. WORKING CLEARANCES ABOUT SERVICE EQUIPTMENT SHALL BE MAINTAINED...
ELE97-00747 INSP - Permanent service3/12/19973/18/19973/18/1997 12:00:00 AMAPASS
03/18/97 403 - service/and outside lights/final
ELE97-00798 INSP - Ele Rough-In/Perm Svc3/17/19973/18/19973/18/1997 12:00:00 AMAPASS
03/18/97 403 -
ELE97-00799 INSP - Ele Rough-In/Perm Svc3/17/19973/18/19973/18/1997 12:00:00 AMAPASS
03/18/97 403 -
ELE97-00805 INSP - T/S and Final3/18/19973/18/19973/18/1997 12:00:00 AMPPASS
03/18/97 403 -
ELE97-00808 INSP - Electrical Rough-In3/18/19973/18/19973/18/1997 12:00:00 AMPPASS
03/18/97 403 - circuit extension from panel to back of house
ELE97-00756 INSP - Ele Rough-In/Perm Svc3/18/19973/18/19973/18/1997 12:00:00 AMPFAIL
03/18/97 403 - AFTER 3:00 BCEC: 1205-C. IN-HOUSE FAN TIMER SWITCH REQUIRED IN ADDITION TO MANUAL NEC: 250-81(C). CONCRETE INCASED GROUNDING ELECTRODE SHALL BE REQUIRED, CONSTRUCTION). NEC: 250-114(A). METAL BOXES SHALL HAVE GROUNDING SCREW
ELE97-00791 INSP - Permanent service3/17/19973/18/19973/18/1997 12:00:00 AMPN.R.
EARLY P.M. CONTRACTOR NEEDED ADDITIONAL MATERIAL FOR COMPLETION, WILL RESCHEDULE...MB
ELE96-03772 INSP - Final3/17/19973/18/19973/18/1997 12:00:00 AMPFAIL
03/18/97 403 - REIN UNABLE TO INSPECT GARAGE DUE TO STORAGE OF CONSTRUCTION MATERIAL THERIN.