Inspections for the day of: Thursday, March 18, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03168 ELE-Aging Inspection3/18/20043/18/20043/18/2004 12:00:00 AM NH
called left message 3/18/2004 11:04:35 AM
ELE04-00295 Final3/16/20043/18/20043/18/2004 12:00:00 AMAPASS
###-#### BRINDA OF TERRY ###-####; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE03-02798 Final3/17/20043/18/20043/18/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
signed T/O pending core and shell final 3/18/2004 9:41:10 AM
ELE03-03707 Final3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
ed; Phone #: ###-#### Internet Inspection Request from: Annette Moore
210.52(C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5).
countertops are in dining room
406.3 General Installation Requirements.
Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.3(A) through (F).
(B) To Be Grounded. Receptacles and cord connectors that have grounding contacts shall have those contacts effectively grounded.
in several locations.
3/18/2004 9:11:08 AM
ELE04-00713 Temporary Service3/17/20043/18/20043/18/2004 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
T/S U/G Ok 3/18/2004 9:58:35 AM
ELE03-02942 Final3/18/20043/18/20043/18/2004 12:00:00 AMPFAIL
sue PLEASE CALL FIRST SO SUE CAN GET THE DOOR UN-LOCKED FOR YOU; Phone #: ###-#### Internet Inspection Request from: Darla Downs
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.
(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(6) Kitchens
several locations
210.52(C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5).
pininsula requires above counter recep 3/18/2004 10:59:51 AM