ELE03-03168
| ELE-Aging Inspection | 3/18/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | | NH |
|
|
called left message 3/18/2004 11:04:35 AM
|
ELE04-00295
| Final | 3/16/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | A | PASS |
|
|
###-#### BRINDA OF TERRY ###-####; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
ELE03-02798
| Final | 3/17/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | A | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
signed T/O pending core and shell final 3/18/2004 9:41:10 AM
|
ELE03-03707
| Final | 3/17/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | A | FAIL |
|
|
ed; Phone #: ###-#### Internet Inspection Request from: Annette Moore
210.52(C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5).
countertops are in dining room
406.3 General Installation Requirements.
Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.3(A) through (F).
(B) To Be Grounded. Receptacles and cord connectors that have grounding contacts shall have those contacts effectively grounded.
in several locations.
3/18/2004 9:11:08 AM
|
ELE04-00713
| Temporary Service | 3/17/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
T/S U/G Ok 3/18/2004 9:58:35 AM
|
ELE03-02942
| Final | 3/18/2004 | 3/18/2004 | 3/18/2004 12:00:00 AM | P | FAIL |
|
|
sue PLEASE CALL FIRST SO SUE CAN GET THE DOOR UN-LOCKED FOR YOU; Phone #: ###-#### Internet Inspection Request from: Darla Downs
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.
(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(6) Kitchens
several locations
210.52(C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5).
pininsula requires above counter recep 3/18/2004 10:59:51 AM
|