Inspections for the day of: Thursday, March 18, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00021 INSP-Final Inspection3/12/20043/18/20043/18/2004 12:00:00 AMAFAIL
Resubmit fire alarm plans that include all devices including the second dry pipe valve, backflow preventor and the additional three duct smoke detectors. End of line voltage on the notification circuits exceeds 21.6 volts(nfpa 72, 7.3.2.3). Provide verification/explanation on resubmittals on why remaining hvac units do not have automatic shutdown per IMC. Office and corridor areas that open into the new addition must be brought up to code compliance. Only the items listed above have been inspected and addressed. All other items to be verified when resubmitted plans have been issued 3/18/2004 9:41:04 AM
FIR04-00060 INSP-Final Inspection3/16/20043/18/20043/18/2004 12:00:00 AMAFAIL
need shell system finaled. Everything else is ok 3/18/2004 9:48:55 AM
FIR04-00094 INSP-Final Inspection3/16/20043/18/20043/18/2004 12:00:00 AMAFAIL
Ok to final when shell is done 3/18/2004 9:53:40 AM
FIR04-00104 INSP-Alarm Testing3/16/20043/18/20043/18/2004 12:00:00 AMAFAIL
a/v's to comply with note #3. Provide additional duct smoke detectors on hvac units in the mark monitor space. Provide sample tubes for duct smoke detectors. Test remaining duct smoke detectors. Provide fax of signals. 3/18/2004 9:51:29 AM 3/18/2004 9:51:45 AM
FIR04-00084 INSP-Final Inspection3/16/20043/18/20043/18/2004 12:00:00 AMAPASS
fire sprinklers finaled 3/18/2004 1:16:55 PM
BLD02-00699 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
Paint curbing and final sprinklers and alarms 3/18/2004 9:52:42 AM
BLD04-00041 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
Ok to final when shell is done 3/18/2004 9:54:57 AM
BLD04-00042 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
Ok to final when shell has been done 3/18/2004 9:54:29 AM
BLD03-01797 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMACANC
Did not due life safety since fire alarm failed 3/18/2004 9:41:32 AM
BLD03-01356 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
Provide fire sprinkler protection in the gas closet per the review notes. Provide verification that the exhaust tubes on the duct smoke detectors can have inlet holes as the installation instructions do not shown this 3/18/2004 10:34:13 AM
BLD03-03046 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAFAIL
Provide suite number per review note #2. Provide approved door hardware on the exterior door of office 102. Door hardware on the main entry exit is mounted backwards and won't allow exiting. Provide fire extinguisher with current inspection tag and mounted 48" above finish floor. 3/18/2004 11:45:18 AM
BLD03-02216 FIRE-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMAPASS
fire life safety finaled. Hvac unit did not require automatic shutdown 3/18/2004 11:07:08 AM
FIR04-00088 INSP-Final Inspection3/17/20043/18/20043/18/2004 12:00:00 AMPFAIL
Upright sprinkler heads in the warehouse along the wall the runs north/south are overspaced off of the wall. Plans show the uprights there but their not. All of the ceiling tile was in so i could not verify pipe and hangers above the offices. Existing trapeze hangers don't conform to review note #32 and the earth quake bracing is attached to the bottom chord of the trusses. See review note #34. 3/18/2004 3:35:38 PM
FIR02-00347 INSP-Final Inspection3/18/20043/18/20043/18/2004 12:00:00 AMPCANC
forward flush
MIS04-00086 FIR-Final3/16/20043/18/20043/18/2004 12:00:00 AMPPASS
life safety finaled 3/18/2004 1:56:09 PM