Inspections for the day of: Friday, March 18, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00494 Electrical Rough-In3/15/20053/18/20053/18/2005 12:00:00 AMAPASS
rough in Internet Inspection Request from: Andy Rose ok 3/18/2005 8:24:59 AM
ELE05-00718 Electrical Rough-In3/16/20053/18/20053/18/2005 12:00:00 AMAPART
underground conduit Internet Inspection Request from: Lee VanSchoiack ###-#### u/g ok called about new bonding 3 ft out 680.26(C) 3/18/2005 9:00:51 AM
ELE05-00746 Electrical Rough-In3/17/20053/18/20053/18/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Heather Packer ok 3/18/2005 9:32:08 AM
ELE05-00895 Temporary Service3/17/20053/18/20053/18/2005 12:00:00 AMAPASS
aaron ###-#### t/s o/h new ok 3/18/2005 8:03:05 AM
ELE03-03159 Final3/17/20053/18/20053/18/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/17/2005 at 8:56:36 PM. Contact: ###-####. job is a mess owner had someone else do work permit for p/s and 2rooms he rewired almost all of the house, kit wiring not right , bath 20 amp has bedrm and garage on it wall spacing open grds, wires just twisted together in boxes screws in plastic boxes wired cover and no inspection 3/18/2005 3:27:15 PM
ELE05-00831 Final3/18/20053/18/20053/18/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/18/2005 at 8:03:06 AM. Contact: ###-####. ok 3/18/2005 4:01:38 PM
ELE05-00892 Final3/18/20053/18/20053/18/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/18/2005 at 9:13:06 AM. Contact: ###-####. needs #6 or protect #8 GEC this is in hiawatha by address10878 called 3/18/2005 1:16:23 PM
ELE05-00901 Temporary Service3/18/20053/18/20053/18/2005 12:00:00 AMPFAIL
set back off road and about 100 feet north of targee on the east side of road mike ###-#### gfci for 220 V recept, brace or guy pole for t/s for support cor. posted called 3/18/2005 12:43:42 PM
ELE04-03213 Final3/18/20053/18/20053/18/2005 12:00:00 AMPPASS
clyde; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok survey needs bond bushing on end of offset nipple where RE washers are used 3/18/2005 3:22:40 PM
ELE05-00380 Final3/17/20053/18/20053/18/2005 12:00:00 AMPFAIL
BJ; Phone #: ###-#### Internet Inspection Request from: Jan Rice p/s not ready grds not complete, 3/18/2005 2:16:07 PM
ELE05-00866 Permanent Service3/17/20053/18/20053/18/2005 12:00:00 AMPFAIL
Internet Inspection Request from: Lee VanSchoiack cor. posted called 300.3 all wire and cables shall have same voltage rating when mixes together, needs 2 grd rods, 300.4 1 1/4 inches for cables, 300.10 needs bond bushings for RE washers 3/18/2005 1:47:58 PM