Inspections for the day of: Tuesday, March 18, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00759 DOC - Permit Expired3/18/20083/18/20083/18/2008 3:28:00 PMPPASS
ELE07-04086 Final3/18/20083/18/20083/18/2008 2:38:40 PMPPASS
Gene Phone #: ###-#### ok
ELE08-00335 Final3/18/20083/18/20083/18/2008 1:49:58 PMPFAIL
George; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
called needs bulbs in all fixtures, and afci for new bedrm addition
ELE08-00639 Temporary Service3/18/20083/18/20083/18/2008 12:56:07 PMPPASS
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
t/s o/h new ok
ELE08-00644 Final3/18/20083/18/20083/18/2008 12:32:59 PMPFAIL
Keddie Phone #: ###-#### corr
ELE08-00644 Electrical Rough-In3/18/20083/18/20083/18/2008 12:32:41 PMPFAIL
Keddie Phone #: ###-#### called left message shall use emt fittings listed for wet location
ELE07-01088 Final3/17/20083/18/20083/18/2008 11:05:10 AMAPASS
sean Phone #: ###-#### ok card signed
ELE03-01808 DOC - Permit Expired3/18/20083/18/20083/18/2008 10:20:12 AMAPASS
no action on permit
ELE03-01806 DOC - Permit Expired3/18/20083/18/20083/18/2008 10:12:35 AMAPASS
no call for inspection,or action on permit
ELE08-00576 Electrical Rough-In3/17/20083/18/20083/18/2008 9:44:24 AMAFAIL
darrell Phone #: ###-#### corr called 300.4 nail plates 314.16,17,20,43 box fill ,outside light box shall be flush with siding,replace 3 gang broken clamps, no screws allowed in plastic boxes
ELE07-03457 Electrical Rough-In3/17/20083/18/20083/18/2008 8:43:17 AMAPART
joe Note: underground Phone #: ###-####
u/g and pole bases S W parking area ok