Inspections for the day of: Tuesday, March 18, 2008.
Number of inspections: 13
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02158 FIRE-Final Inspection3/11/20083/12/2008 A 
FIR07-00710 INSP-Final Inspection3/18/20083/18/20083/19/2008 1:49:10 PMPFAIL
Need to relocate smoke alarms at four locations including units 305,105, 102 and 203, also need to remove plastic at all apartment unit smoke alarms prior to occupancy.
FIR06-00365 INSP-Final Inspection3/18/20083/18/20083/18/2008 3:11:52 PMPDEFR
Wrong permit number requested for inspection.
BLD06-02528 FIRE-Final Inspection3/17/20083/18/20083/18/2008 3:10:29 PMPFAIL
Provide knox box, need to final fire sprinkler and alarm permits, need closures at doors, not all items reviewed at this time.
FIR07-00937 INSP-Final Inspection3/17/20083/18/20083/18/2008 3:08:51 PMAFAIL
Provide service tag at the riser, provide "911" sign at the outside bell, missing escutcheons at some locations, one blocked head at a kitchen area by an adjacent light fixture.
FIR07-00910 INSP-Alarm Testing3/17/20083/18/20083/18/2008 3:05:26 PMAFAIL
Provide updated map at the FACP, zones need to match plan.
FIR07-01022 INSP-Conference3/18/20083/18/20083/18/2008 2:51:11 PMPDONE
Regarding after hours inspection scheduling.
FIR07-00917 INSP-Sprinkler Rough-in3/17/20083/18/20083/18/2008 2:40:37 PMANR
Lacking access to some areas in need of inspection due to flooring installation underway, inspection rescheduled for 3/19.
BLD06-00077 FIRE-Final Inspection3/18/20083/18/20083/18/2008 2:38:31 PMPPASS
Fire life safety finaled.
BLD05-02630 FIRE-Final Inspection3/17/20083/18/20083/18/2008 1:46:24 PMAPASS
Vanilla permit life safety inspection passed, reversed door swing at the south entrance is acceptable pending plan resubmittals per D. Stuart.
FIR08-00175 INSP-Final Inspection3/17/20083/18/20083/18/2008 1:05:59 PMAPASS
Fire alarm system modifications passed field testing, permit finaled.
FIR07-00997 INSP-Conference3/14/20083/18/20083/18/2008 1:04:32 PMADONE
On site visit regarding the requirement for extended coverage pendent sprinklers at the sales floor area to meet NFPA 13 2002 table 8.8.5.1.2(a) to avoid obstructions to discharge.
BLD07-02307 FIRE-Final Inspection3/17/20083/18/20083/18/2008 12:59:56 PMAPASS
Fire life safety inspection passed, incorrect sample tube placement at two duct detectors repaired while on site, weak battery at the EM light in the electrical room to be replaced as agreed.