BLD05-02158
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | | A | |
|
|
|
FIR07-00710
| INSP-Final Inspection | 3/18/2008 | 3/18/2008 | 3/19/2008 1:49:10 PM | P | FAIL |
|
|
Need to relocate smoke alarms at four locations including units 305,105, 102 and 203, also need to remove plastic at all apartment unit smoke alarms prior to occupancy.
|
FIR06-00365
| INSP-Final Inspection | 3/18/2008 | 3/18/2008 | 3/18/2008 3:11:52 PM | P | DEFR |
|
|
Wrong permit number requested for inspection.
|
BLD06-02528
| FIRE-Final Inspection | 3/17/2008 | 3/18/2008 | 3/18/2008 3:10:29 PM | P | FAIL |
|
|
Provide knox box, need to final fire sprinkler and alarm permits, need closures at doors, not all items reviewed at this time.
|
FIR07-00937
| INSP-Final Inspection | 3/17/2008 | 3/18/2008 | 3/18/2008 3:08:51 PM | A | FAIL |
|
|
Provide service tag at the riser, provide "911" sign at the outside bell, missing escutcheons at some locations, one blocked head at a kitchen area by an adjacent light fixture.
|
FIR07-00910
| INSP-Alarm Testing | 3/17/2008 | 3/18/2008 | 3/18/2008 3:05:26 PM | A | FAIL |
|
|
Provide updated map at the FACP, zones need to match plan.
|
FIR07-01022
| INSP-Conference | 3/18/2008 | 3/18/2008 | 3/18/2008 2:51:11 PM | P | DONE |
|
|
Regarding after hours inspection scheduling.
|
FIR07-00917
| INSP-Sprinkler Rough-in | 3/17/2008 | 3/18/2008 | 3/18/2008 2:40:37 PM | A | NR |
|
|
Lacking access to some areas in need of inspection due to flooring installation underway, inspection rescheduled for 3/19.
|
BLD06-00077
| FIRE-Final Inspection | 3/18/2008 | 3/18/2008 | 3/18/2008 2:38:31 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD05-02630
| FIRE-Final Inspection | 3/17/2008 | 3/18/2008 | 3/18/2008 1:46:24 PM | A | PASS |
|
|
Vanilla permit life safety inspection passed, reversed door swing at the south entrance is acceptable pending plan resubmittals per D. Stuart.
|
FIR08-00175
| INSP-Final Inspection | 3/17/2008 | 3/18/2008 | 3/18/2008 1:05:59 PM | A | PASS |
|
|
Fire alarm system modifications passed field testing, permit finaled.
|
FIR07-00997
| INSP-Conference | 3/14/2008 | 3/18/2008 | 3/18/2008 1:04:32 PM | A | DONE |
|
|
On site visit regarding the requirement for extended coverage pendent sprinklers at the sales floor area to meet NFPA 13 2002 table 8.8.5.1.2(a) to avoid obstructions to discharge.
|
BLD07-02307
| FIRE-Final Inspection | 3/17/2008 | 3/18/2008 | 3/18/2008 12:59:56 PM | A | PASS |
|
|
Fire life safety inspection passed, incorrect sample tube placement at two duct detectors repaired while on site, weak battery at the EM light in the electrical room to be replaced as agreed.
|