Inspections for the day of: Thursday, March 18, 2010.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00655 FIR-Aging Inspection3/18/20103/18/20103/24/2010 7:47:35 AM NR
Permit information forwarded to Stephanie and to Scott for further action.
FIR09-00734 INSP-Final Inspection3/17/20103/18/20103/18/2010 3:36:28 PMAFAIL
Forward flush of the backflow needs to be performed, certification of the backflow, service tag on the riser, head box verified.....ect. The interconnection with the fire alarm panel tested ok. I spoke to Doug, the superintendant, and with Tom the building inspector about the need for the one hour riser room. Their are holes in the wall and gaps around all of the exiting piping.
FIR10-00049 INSP-Final Inspection3/18/20103/18/20103/18/2010 3:34:26 PMPFAIL
Trouble signals did not annuciate at the facp as required, battery was not a 8ah, as-builts reflecting the additional flow switch and the two additional tamper switches. Also the order in which the devices were tested was not reflected in the order that the central station received them. Electrician was going to provide the lock for the dedicated circuit. I let Doug know that signage would be required for the riser room/facp room door.
BLD10-00431 FIRE-Final Inspection3/15/20103/18/20103/18/2010 11:06:04 AMAFAIL
See the city approved plans for locations of deficiencies. They include repairing the lower level exit signs/emergency lighting, providing up to date annual inspection for all fire extinguishers, providing approved door hardware on the exterior exit doors, repairing the hanging insulation and providing a building address.
FIR10-00071 INSP-Sprinkler Rough-in3/17/20103/18/20103/18/2010 9:12:28 AMAPASS
All hard lid areas are ok to cover. Additional sprinkler pendants are required to be installed, as per plan, in both window areas on both sides of the main entry. One side is a ceiling pocket that does not meet all of the requirements of NFPA 13 - 8.6.7 and the other side has blockage caused by a wall.
FIR09-00689 INSP-Final Inspection3/17/20103/18/20103/18/2010 9:05:38 AMAPASS
Permit finaled
FIR09-00743 INSP-Final Inspection3/17/20103/18/20103/18/2010 9:05:15 AMAPASS
Permit finaled