FIR14-00081
| INSP-Final Inspection | 3/18/2014 | 3/18/2014 | 3/20/2014 10:55:37 AM | P | PASS |
|
|
Hood suppression systems operated correctly under test conditions. Permit finaled.
|
FIR13-00252
| INSP-Final Inspection | 3/17/2014 | 3/18/2014 | 3/20/2014 10:53:11 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR13-00648
| INSP-Final Inspection | 3/12/2014 | 3/18/2014 | 3/18/2014 3:07:04 PM | P | PART |
|
|
Completed fire alarm acceptance testing. Necessary adjustments made while on site. Scope of work completed. Final pending installation of a knox box per review note item #13.
|
BLD13-02108
| FIRE-Final Inspection | 3/17/2014 | 3/18/2014 | 3/18/2014 2:32:28 PM | P | PASS |
|
|
Fire life safety inspection completed. Need to add identification labels at refrigerant alarms, noted two fire extingusihers at the basement level overdue annual certification. To be completed prior to structural final.
|
BLD14-00168
| FIRE-Final Inspection | 3/17/2014 | 3/18/2014 | 3/18/2014 2:29:36 PM | A | DONE |
|
|
david or jessie at ###-#### Phone #: ###-####
|
FIR13-00713
| INSP-Sprinkler Rough-in | 3/17/2014 | 3/18/2014 | 3/18/2014 11:29:52 AM | A | FAIL |
|
|
First floor corrections include; missing hangers at two locations, piping to SW heads incompleted, provide intermediate temp heads at the furnace closets, min. distance between heads is not met at two units, a swing joint at the west end unit appears to be "dry fit".
|
FIR14-00081
| INSP-Final Inspection | 3/17/2014 | 3/18/2014 | 3/18/2014 10:50:29 AM | A | NR |
|
|
dave Phone #: ###-#### * Equipment not ready for testing at this time- Inspection to be rescheduled.
|
FIR14-00124
| INSP-Sprinkler Rough-in | 3/17/2014 | 3/18/2014 | 3/18/2014 9:45:16 AM | A | PART |
|
|
Fire sprinkler work at the mens and womens restroom, utility, hallway and cooler approved for cover as marked/dated on approved plan set.
|