FIR15-00047
| INSP-Alarm Testing | 3/17/2015 | 3/18/2015 | 3/19/2015 2:04:31 PM | A | PASS |
|
|
Fire alarm work passed functional testing.
|
FIR15-00030
| INSP-Alarm Testing | 3/17/2015 | 3/18/2015 | 3/19/2015 2:03:54 PM | A | PASS |
|
|
Fire alarm work passed functional testing.
|
FIR15-00039
| INSP-Sprinkler Rough-in/Hydro | 3/18/2015 | 3/18/2015 | 3/18/2015 7:11:05 PM | P | PART |
|
|
Overhead rough-in inspection completed. Need to verify insulation fill above the vehicle bay at the non-sprinklered combustible concealed spaces to meet allowable exceptions per NFPA 13, need to relocate one overspaced upright above the report room. OH hydrostatic test passed.
|
FIR14-00783
| INSP-Sprinkler Rough-in | 3/17/2015 | 3/18/2015 | 3/18/2015 2:01:26 PM | A | PART |
|
|
Inspection for end caps at manifold and ductile risers/90's at tank supply and draft piping. Thrust blocking is not yet provided. Photo documentation recorded.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 3/13/2015 | 3/18/2015 | 3/18/2015 12:54:37 PM | A | DEFR |
|
|
|
FIR14-00867
| INSP-Sprinkler Rough-in/Hydro | 3/18/2015 | 3/18/2015 | 3/18/2015 12:52:53 PM | A | NR |
|
|
don forester Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD15-00480
| FIRE-Conference | 3/17/2015 | 3/18/2015 | 3/18/2015 12:51:48 PM | A | DONE |
|
|
On site conference and discussion with contractor regarding fire life safety inspection items, project related fire sprinkler and alarm work, egress door hardware, etc.
|