Inspections for the day of: Wednesday, March 18, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00047 INSP-Alarm Testing3/17/20153/18/20153/19/2015 2:04:31 PMAPASS
Fire alarm work passed functional testing.
FIR15-00030 INSP-Alarm Testing3/17/20153/18/20153/19/2015 2:03:54 PMAPASS
Fire alarm work passed functional testing.
FIR15-00039 INSP-Sprinkler Rough-in/Hydro3/18/20153/18/20153/18/2015 7:11:05 PMPPART
Overhead rough-in inspection completed. Need to verify insulation fill above the vehicle bay at the non-sprinklered combustible concealed spaces to meet allowable exceptions per NFPA 13, need to relocate one overspaced upright above the report room. OH hydrostatic test passed.
FIR14-00783 INSP-Sprinkler Rough-in3/17/20153/18/20153/18/2015 2:01:26 PMAPART
Inspection for end caps at manifold and ductile risers/90's at tank supply and draft piping. Thrust blocking is not yet provided. Photo documentation recorded.
FIR14-00815 INSP-Sprinkler Rough-in3/13/20153/18/20153/18/2015 12:54:37 PMADEFR
FIR14-00867 INSP-Sprinkler Rough-in/Hydro3/18/20153/18/20153/18/2015 12:52:53 PMANR
don forester Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD15-00480 FIRE-Conference3/17/20153/18/20153/18/2015 12:51:48 PMADONE
On site conference and discussion with contractor regarding fire life safety inspection items, project related fire sprinkler and alarm work, egress door hardware, etc.