ELE13-02165
| ELE-Aging Inspection | 3/18/2016 | 3/18/2016 | 3/23/2016 2:34:16 PM | | DONE |
|
|
Drove by. Signs are not present on units noted.
|
ELE12-02580
| ELE-Aging Inspection | 3/18/2016 | 3/18/2016 | 3/18/2016 3:02:53 PM | | PASS |
|
|
Waiting on contractor
|
MIS16-00070
| ELE-Conference | 3/15/2016 | 3/18/2016 | 3/18/2016 2:54:21 PM | P | DONE |
|
|
Ray (fire) ###-#### No return phone calls from contacts. Unable to locate illegal work.
|
MIS16-00070
| ELE-Final | 3/18/2016 | 3/18/2016 | 3/18/2016 2:54:03 PM | P | PASS |
|
|
Ray (fire) ###-#### Final ok
|
ELE13-00373
| ELE-Aging Inspection | 3/18/2016 | 3/18/2016 | 3/18/2016 2:42:08 PM | | PASS |
|
|
Waiting on contractor
|
ELE16-00826
| Final | 3/18/2016 | 3/18/2016 | 3/18/2016 2:29:23 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brian Caruso No access to garage to check panel. 408.7- Unused breaker openings shall be closed.
|
MIS16-00077
| ELE-Conference | 3/18/2016 | 3/18/2016 | 3/18/2016 1:52:40 PM | P | DONE |
|
|
possible electrical work with no permit No work performed yet scheduled reinspect 3/23/16. At time of inspection drywall removed and painting bare studs and attic areas to seal odors.
|
ELE16-00536
| Electrical Rough-In | 3/18/2016 | 3/18/2016 | 3/18/2016 1:32:33 PM | P | PASS |
|
|
Larry-cover Phone #: ###-#### Interior of emissions office rough in ok cover
|
ELE16-00802
| Rough-In Permanent Service | 3/15/2016 | 3/18/2016 | 3/18/2016 1:05:55 PM | P | PASS |
|
|
Idaho Power To Disconnect At 9AM. Phone #: ###-#### Inspection requested via web by Louis Keller Hot tub rough in ok p/s o/h rec ok
|
ELE15-03903
| Final | 3/17/2016 | 3/18/2016 | 3/18/2016 12:40:38 PM | A | FAIL |
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 406.4(D)(2)- Grounding type receptacle outlet installed on an ungrounded circuit. either GFCI protect or change to a 2-wire receptacle. 410.10(D)- All luminaires located with in 3' horizontally and 8' vertical of tub edge or shower threshold shall be damp location rated.
|
ELE15-03637
| Final | 3/18/2016 | 3/18/2016 | 3/18/2016 11:34:44 AM | P | FAIL |
|
|
210.8- All bathroom receptacle outlets shall have GFCI protection. Up bath. Main bath open neutral. 210.12- Up loft with closet rods in closet shall have AFCI protection.
|
GCE15-00167
| GCE-Final | 3/17/2016 | 3/18/2016 | 3/18/2016 10:48:12 AM | A | FAIL |
|
|
Brandon ###-#### 110.22- AC disconnect shall be identified as to which unit it supplys. 210.8- All 120 volt 15 or 20 amp receptacle outlets installed with in 6' of a sink shall have GFCI protection. 410.16- Incondescent and LED luminaires shall have a minimum of 12" shelf clearance.
|
ELE15-03687
| Final | 3/17/2016 | 3/18/2016 | 3/18/2016 9:45:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman Temp pole removed from lot. Final ok
|
ELE16-00866
| Rough-In Permanent Service | 3/18/2016 | 3/18/2016 | 3/18/2016 8:47:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|