Inspections for the day of: Friday, March 18, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02165 ELE-Aging Inspection3/18/20163/18/20163/23/2016 2:34:16 PM DONE
Drove by. Signs are not present on units noted.
ELE12-02580 ELE-Aging Inspection3/18/20163/18/20163/18/2016 3:02:53 PM PASS
Waiting on contractor
MIS16-00070 ELE-Conference3/15/20163/18/20163/18/2016 2:54:21 PMPDONE
Ray (fire) ###-#### No return phone calls from contacts. Unable to locate illegal work.
MIS16-00070 ELE-Final3/18/20163/18/20163/18/2016 2:54:03 PMPPASS
Ray (fire) ###-#### Final ok
ELE13-00373 ELE-Aging Inspection3/18/20163/18/20163/18/2016 2:42:08 PM PASS
Waiting on contractor
ELE16-00826 Final3/18/20163/18/20163/18/2016 2:29:23 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brian Caruso
No access to garage to check panel.
408.7- Unused breaker openings shall be closed.
MIS16-00077 ELE-Conference3/18/20163/18/20163/18/2016 1:52:40 PMPDONE
possible electrical work with no permit
No work performed yet scheduled reinspect 3/23/16. At time of inspection drywall removed and painting bare studs and attic areas to seal odors.
ELE16-00536 Electrical Rough-In3/18/20163/18/20163/18/2016 1:32:33 PMPPASS
Larry-cover Phone #: ###-####
Interior of emissions office rough in ok cover
ELE16-00802 Rough-In Permanent Service3/15/20163/18/20163/18/2016 1:05:55 PMPPASS
Idaho Power To Disconnect At 9AM. Phone #: ###-#### Inspection requested via web by Louis Keller Hot tub rough in ok p/s o/h rec ok
ELE15-03903 Final3/17/20163/18/20163/18/2016 12:40:38 PMAFAIL
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
406.4(D)(2)- Grounding type receptacle outlet installed on an ungrounded circuit. either GFCI protect or change to a 2-wire receptacle.
410.10(D)- All luminaires located with in 3' horizontally and 8' vertical of tub edge or shower threshold shall be damp location rated.
ELE15-03637 Final3/18/20163/18/20163/18/2016 11:34:44 AMPFAIL
210.8- All bathroom receptacle outlets shall have GFCI protection. Up bath. Main bath open neutral.
210.12- Up loft with closet rods in closet shall have AFCI protection.
GCE15-00167 GCE-Final3/17/20163/18/20163/18/2016 10:48:12 AMAFAIL
Brandon ###-####
110.22- AC disconnect shall be identified as to which unit it supplys.
210.8- All 120 volt 15 or 20 amp receptacle outlets installed with in 6' of a sink shall have GFCI protection.
410.16- Incondescent and LED luminaires shall have a minimum of 12" shelf clearance.
ELE15-03687 Final3/17/20163/18/20163/18/2016 9:45:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Brandon Hillman Temp pole removed from lot. Final ok
ELE16-00866 Rough-In Permanent Service3/18/20163/18/20163/18/2016 8:47:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok