Inspections for the day of: Wednesday, March 18, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03598 Electrical Rough-In3/18/20203/18/20203/18/2020 2:40:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
314.28- Minimum junction box for feed from main to transformer disconnect shall be 8 times largest conduit. 2"x 8=16" minimum. 12"x 12" installed.
Walked interior lighting and found 2 open boxes which feed roof top fans.
Interior structure grid rough in ok cover and transformer bonding rough in ok cover.
ELE20-00209 Final3/17/20203/18/20203/18/2020 1:58:09 PMPFAIL
Phone #: ###-#### Inspection requested via web by Steven Ragan
110.7- 2 receptacles not working, 1 left of sink and 1 existing on east south wall.
ELE20-00837 Final3/17/20203/18/20203/18/2020 1:18:27 PMPPASS
Please call Patrick at ###-#### 30 minutes prior to arrival so he can have building unlocked for you. Thanks Phone #: ###-#### Inspection requested via web by Winters LLC Final ok
ELE20-00837 Electrical Rough-In3/17/20203/18/20203/18/2020 1:17:32 PMPPASS
Please call Patrick at ###-#### 30 minutes prior to arrival so he can have building unlocked for you. Thanks Phone #: ###-#### Inspection requested via web by Winters LLC Break room grid rough in ok cover
ELE20-00955 Electrical Rough-In3/17/20203/18/20203/18/2020 10:38:21 AMAPASS
Floor plugs in slab Phone #: ###-#### Inspection requested via web by Zane Robertson Underslab rough in ok cover
ELE19-04938 Electrical Rough-In3/17/20203/18/20203/18/2020 10:33:08 AMAFAIL
Floor heat master bath Phone #: ###-#### Inspection requested via web by Zane Robertson 110.3- Cold lead splice shall be located in the floor as per manufacturers instructions.
ELE20-00786 Electrical Rough-In3/17/20203/18/20203/18/2020 10:00:08 AMAPASS
Someone will be there. Call Nik with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan
Bathroom to get new vanity and stool with no electrical changes.
Kitchen rough in ok cover
ELE19-04131 Electrical Rough-In3/17/20203/18/20203/18/2020 9:32:56 AMAPASS
Rough in inspection for vestibule and reception walls and ceilings. Show window areas above mullions. Raised seating wood frame walls. Phone #: ###-#### Inspection requested via web by John Mittleider
Areas noted rough in ok cover.