Inspections for the day of: Wednesday, March 18, 2020.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01030 Final3/16/20203/18/20203/18/2020 3:34:17 PMPPASS
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace only ok
MEC20-01077 Final3/18/20203/18/20203/18/2020 3:17:00 PMPCANC
El-Ada #A-12991; Need flue test as well; Please schedule mid-late afternoon (maybe around 3 if possible) Phone #: ###-#### Inspection requested via web by Loren Bailey- no installed onsite for flue test
MEC20-00852 Rough-in3/18/20203/18/20203/18/2020 3:05:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC20-00852 Pressure Test3/18/20203/18/20203/18/2020 3:04:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location
MEC19-03890 Final3/18/20203/18/20203/18/2020 2:31:55 PMPFAIL
Please call Don on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- need to remove all ceiling tiles to view duct work that was installed to look at insulation and flex to registers- all ceiling tiles installed
MEC20-01151 Final3/18/20203/18/20203/18/2020 1:56:44 PMPPASS
Please call Francis to verify inspection time. Flue pipe pressure will need to be witnessed. Phone #: ###-#### Inspection requested via web by max sanders- furnace a/c coil co locking caps ok
MEC20-01152 Final3/18/20203/18/20203/18/2020 1:33:54 PMPPASS
please call Ben to verify inspection time Phone #: ###-#### Inspection requested via web by max sanders- furnace in crawl co ok
MEC20-01091 Final3/17/20203/18/20203/18/2020 12:56:59 PMPPART
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- RTU finals ok- need 3 RTUs smoke detetors testing passed to final this permit out
MEC20-00892 Rough-in3/17/20203/18/20203/18/2020 11:20:08 AMAPASS
R/I Inspection. Please contact Robbie prior to arrival. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator- R/I ok
MEC20-01111 Final3/17/20203/18/20203/18/2020 11:04:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace in crawl a/c coil co locking caps ok
MEC10-02322 Conference3/17/20203/18/20203/18/2020 10:32:51 AMADONE
Steve Phone #: ###-####- mantel height both fireplaces ok per discussion and installation instructions
MEC10-02322 Final3/18/20203/18/20203/18/2020 10:31:50 AMAPASS
Steve Phone #: ###-####- final ok
MEC20-01130 Rough-in3/17/20203/18/20203/18/2020 10:18:50 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson
1- need city approved man j onsite none found
2- need inner liner on exhaust fan flex seal to plastic fan connection
3- all spot welds on return air/ transfer boots need sealed
4- need to seal dryer duct to termination box i wall

left notice front window
MEC20-00260 Final3/17/20203/18/20203/18/2020 10:17:03 AMAFAIL
GARAGE CODE: 7445 Phone #: ###-#### Inspection requested via web by Kristy Watson
1- condenser model # doesnt match man j- resubmit or change out to right one
2- a/c service ports need locking caps installed
MEC20-01130 Pressure Test3/18/20203/18/20203/18/2020 10:11:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Kristy Watson- 20lb gas pass tagged meter location
MEC19-03890 Final3/18/20203/18/20203/18/2020 9:38:19 AMPCANC
Please call Don on your way - ###-#### Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
MEC20-01140 Pressure Test3/17/20203/18/20203/18/2020 9:29:27 AMAPASS
Call Greg if you have any questions 2084400662 Phone #: ###-#### Inspection requested via web by Greg Mendiola- 20lb gass x 2 underground- ok to backfill- call in final when completed
MEC20-00736 Final3/17/20203/18/20203/18/2020 9:07:06 AMAPASS
Kimber ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
MEC20-01147 Conference3/17/20203/18/20203/18/2020 8:56:27 AMADONE
Phone #: ###-#### Inspection requested via web by Rubin Chervak- discussed condenser location- will need conference with bld inspector on fire blocking/wall
MEC20-01146 Conference3/17/20203/18/20203/18/2020 8:55:41 AMADONE
Phone #: ###-#### Inspection requested via web by Rubin Chervak- discussed condenser location
MEC20-01148 Conference3/17/20203/18/20203/18/2020 8:55:18 AMADONE
Phone #: ###-#### Inspection requested via web by Rubin Chervak- discussed condenser location- need bld conference for fire block penetration
MEC20-01149 Conference3/17/20203/18/20203/18/2020 8:54:35 AMADONE
Phone #: ###-#### Inspection requested via web by Rubin Chervak- discussed condenser location
MEC19-03793 Mec-Aging Inspection3/18/20203/18/20203/18/2020 7:46:25 AM CANC