MEC20-01122
| Final | 3/17/2020 | 3/18/2020 | 3/18/2020 3:44:08 PM | P | CANC |
|
|
Please inspect early PM and call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - should have been a R/I not a final will need to see range hood tied into ducting
|
MEC20-01122
| Rough-in | 3/18/2020 | 3/18/2020 | 3/18/2020 3:43:29 PM | P | PASS |
|
|
Please inspect early PM and call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok
|
MEC20-01137
| Pressure Test | 3/18/2020 | 3/18/2020 | 3/18/2020 3:34:02 PM | P | PASS |
|
|
CHANGED OUT GAUGES TO 30LB AND READY FOR REINSPECTION. I LEFT MY PHONE NUMBER AGAIN JUST IN CASE- STEVE DALE Phone #: ###-#### Inspection requested via web by Rick Montgomery - 20lb gas pressure test ok - tagged meter location
|
MEC20-01127
| Pressure Test | 3/18/2020 | 3/18/2020 | 3/18/2020 3:22:44 PM | P | FAIL |
|
|
Please contact Jasper and give him 30 minutes to meet you on site if needed. Phone #: ###-#### Inspection requested via web by Ted Dumont Inc. - 20lb gas pressure test fail gauge under 20lb
|
MEC20-00746
| Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 3:17:06 PM | P | PASS |
|
|
R/I Inspection. Please contact Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator -R/I ok
|
MEC20-00538
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 2:37:35 PM | P | PASS |
|
|
Please provide final inspection at 380 Park Center in Boise for 3rd floor remodel job 42437. ACS contact person is Todd ###-####. Inspection requested via web by Kathy Youngkin - final ok
|
MEC19-05400
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 2:25:04 PM | P | PASS |
|
|
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
MEC19-05401
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 2:24:57 PM | P | PASS |
|
|
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
MEC20-00908
| Final | 3/5/2020 | 3/18/2020 | 3/18/2020 2:24:47 PM | P | CANC |
|
|
###-#### - Nat
|
MEC20-01053
| Final | 3/12/2020 | 3/18/2020 | 3/18/2020 2:24:22 PM | P | PASS |
|
|
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - furnace ac coil co ok
|
MEC19-02873
| Final | 3/17/2020 | 3/18/2020 | 3/18/2020 1:59:01 PM | P | PASS |
|
|
Please call prior to arrival to ensure the corrections are made. Kay Felt Phone #: ###-#### Inspection requested via web by Andrea Grigsby - final ok
|
MEC20-00770
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 1:19:38 PM | P | PASS |
|
|
Please call Jason with any questions ###-#### Phone #: ###-#### Inspection requested via web by Brenda Baxter - final ok
|
MEC20-00771
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 1:16:37 PM | P | NR |
|
|
Please call Jason with any questions ###-#### Phone #: ###-#### Inspection requested via web by Brenda Baxter - need to see shut off valve within 6' of firepit
|
MEC20-01133
| Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 12:00:47 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - need approved Man J onsite - b vent needs replaced screw went through inner liner
|
MEC20-01133
| Pressure Test | 3/17/2020 | 3/18/2020 | 3/18/2020 11:59:41 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - 20lb gas pressure test ok - tagged meter location
|
MEC20-00324
| Final | 3/17/2020 | 3/18/2020 | 3/18/2020 11:39:09 AM | A | PASS |
|
|
Please call Vadim when you are on your way. ###-#### Phone #: ###-#### Inspection requested via web by Brett Shannon - final ok
|
MEC20-01114
| Pressure Test | 3/16/2020 | 3/18/2020 | 3/18/2020 11:23:20 AM | A | PASS |
|
|
Inspection if possible between 9-10 for pressure test. Phone #: ###-#### Inspection requested via web by Teresa Costello - 20lb gas pressure test ok
|
MEC20-00908
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 10:49:02 AM | A | PASS |
|
|
can you call me about a half hour before heading over? Phone #: ###-#### Inspection requested via web by Nat Golden - furnace only co ok
|
MEC20-01124
| Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 10:20:57 AM | A | FAIL |
|
|
code 4810 Phone #: ###-#### Inspection requested via web by Angie Thome - 20lb gas pressure test fail - need to see low combustion air opening - fresh air needs a back draft damper - need information on fireplace chimney - CSST gas line needs proper nail plates installed
|
MEC20-01124
| Pressure Test | 3/17/2020 | 3/18/2020 | 3/18/2020 10:19:49 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Angie Thome - 20lb gas pressure test fail gauge under 20lb
|
MEC20-01102
| Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 9:50:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lindsey Stegemann - fireplace R/I ok
|
MEC19-05075
| Final | 3/18/2020 | 3/18/2020 | 3/18/2020 9:31:05 AM | A | PASS |
|
|
Contact Francisco ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - final ok
|
MEC20-01137
| Pressure Test | 3/17/2020 | 3/18/2020 | 3/18/2020 9:04:36 AM | A | FAIL |
|
|
UNIT #7 FOR THIS PROPERTY- PRESSURED GAS LINE IS LOCATED ON EXTERIOR OF BUILDING AND YOU CAN ACCESS.
I LEFT MY PHONE NUMBER IF YOU NEED SOMEONE TO MEET YOU THERE, MY NAME IS STEVE DALE Phone #: ###-#### Inspection requested via web by Rick Montgomery - gas pressure test needs to be on a 30lb gauge at 20lb
|
MEC18-05436
| Mec-Aging Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 8:43:11 AM | | PASS |
|
|
WIP
|
MEC19-03806
| Mec-Aging Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 8:42:58 AM | | PASS |
|
|
Doc Permit Finaled ok
|
MEC19-03806
| DOC - Permit Finaled | 3/18/2020 | 3/18/2020 | 3/18/2020 8:42:44 AM | A | PASS |
|
|
Doc Permit Finaled ok
|
MEC19-03787
| Mec-Aging Inspection | 3/18/2020 | 3/18/2020 | 3/18/2020 8:42:21 AM | | FAIL |
|
|
Permit has not been active since being issued on 8-23-19. Schedule inspection with owner if work is finished. Permit will expire at next mechanical aging inspection if not active.
|
MEC20-01096
| Rough-in | 3/17/2020 | 3/18/2020 | 3/18/2020 8:41:01 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - R/I ok - do not cover sticker in window until fireplace R/I done by others
|
MEC20-01096
| Pressure Test | 3/17/2020 | 3/18/2020 | 3/18/2020 8:39:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas pressure test ok - tagged meter location
|