Inspections for the day of: Wednesday, March 19, 1997.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE95-01339 INSP - Final3/19/19973/19/19973/20/1997 12:00:00 AMPFAIL
03/20/97 315 - 14 failed jf cor. and $30.00 fee due posted NEC,384-4, 11 exception #2, 220-10, 250-113, BCC, 4-5-54
ELE96-02938 INSP - Electrical Rough-In3/19/19973/19/19973/20/1997 12:00:00 AMPPART
03/20/97 315 - PARTIAL CEILING 09 ok jf about 90% of ceiling
ELE97-00817 INSP - Ele Rough-In/Perm Svc3/19/19973/19/19973/19/1997 12:00:00 AM PASS
/ / 315 - 09&53 ok jf 12rms 1a/c 200a u/g new
ELE97-00817 INSP - Ele Rough-In/Perm Svc3/18/19973/19/19973/19/1997 12:00:00 AMAFAIL
03/19/97 315 - ASAP PLEASE 09&53 failed jf cor. & do not cover posted N required L rm 250-92(b) GEC & SEVICE ENCLOSURE shall be electrically continuous, 350-20 shall not cover 90 degree flex fitting back of servic panel also noted 300-14
ELE97-00818 INSP - T/S and Final3/18/19973/19/19973/19/1997 12:00:00 AMAPASS
03/19/97 315 - 49&14 ok jf u/g new
ELE97-00754 INSP - Ele Rough-In/Perm Svc3/18/19973/19/19973/19/1997 12:00:00 AMAPASS
09&53 ok jf 10rms 1a/c 200a u/g new cor made
ELE97-00813 INSP - T/S and Final3/18/19973/19/19973/19/1997 12:00:00 AMAPASS
03/19/97 315 - 49&14 ok jf u/g new
ELE95-01339 INSP - Final3/18/19973/19/19973/19/1997 12:00:00 AMAFAIL
03/19/97 315 - 14 failed will post cor. notice after lunch for Royal Ele inspected jf
ELE97-00824 INSP - Electrical Rough-In3/19/19973/19/19973/19/1997 12:00:00 AMPPASS
03/19/97 315 - two rooms 09 ok jf res. rem.
ELE97-00828 INSP - Electrical Rough-In3/19/19973/19/19973/19/1997 12:00:00 AMPPART
03/19/97 315 - WIRING PLUGS NAD LIGHTS UNIT 375 09 ok jf part.
ELE97-00417 INSP - Final3/19/19973/19/19973/19/1997 12:00:00 AMPPASS
03/19/97 315 - 14 ok jf
ELE97-00620 INSP - Final3/19/19973/19/19973/19/1997 12:00:00 AMPPASS
03/19/97 315 - suite 210 /call rex at ###-#### to set time to meet. so h work is. 14 ok jf