ELE04-00681
| Rough-In Permanent Service | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/18/2004 at 9:46:50 AM. Contact: ###-####. r/i ok
p/s u/g new ok 3/19/2004 12:56:17 PM
|
ELE04-00140
| Final | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 3/18/2004 at 11:15:24 AM. Contact: ###-####. met contractor 3/19/2004 10:53:53 AM
|
ELE04-00643
| Electrical Rough-In | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/18/2004 at 1:09:04 PM. Contact: ###-####. cor. posted called outlet spacing all locations walls, and countertops, box fill nail plates and 11/4" all make shall be complete COW 3/19/2004 10:24:17 AM
|
ELE04-00755
| Final | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | FAIL |
|
|
###-#### ALAN cor. posted called terminate grd at neutral bus, install bond bushing on fles con. at sprinkler timer or better to use non-metallic sealtight 3/19/2004 9:31:54 AM
|
ELE04-00223
| Electrical Rough-In | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | FAIL |
|
|
call 1st before insp-- ###-####- or ###-####- bart cor. posted called needs 2 grd rods, grd or bond water system shall not use #12 white as phase conductor, needs new box for dyer recept, clean paint off pipe at grd clamp, do not double 2 circuits on 1 breaker , address neutral to phase load 3/19/2004 9:01:07 AM
|
ELE04-00643
| Electrical Rough-In | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | FAIL |
|
|
plans at site do not match the job
|
ELE03-03998
| Final | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | A | CANC |
|
|
permit holder does not own property anymore, new owner has permit
|
ELE04-00684
| Permanent Service | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | P | PASS |
|
|
p/s u/g new ok
|
ELE04-00684
| Electrical Rough-In | 3/18/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/18/2004 at 6:30:15 AM. Contact: ###-####. r/i and conference ok see added p/s
3/19/2004 12:25:02 PM
|
ELE03-03402
| Final | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | P | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted 110.26 clearence for panel, ,, breakers ntoo high 404.8, 250.64(C) shall not splice GEC, owner shall show proof of permits and inspections for coffee shack 3/19/2004 4:26:55 PM
|
ELE04-00692
| Electrical Rough-In | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/19/2004 at 10:10:25 AM. Contact: ###-####. u/g r/i ok
3/19/2004 3:59:41 PM
|
ELE02-02940
| Conference | 3/19/2004 | 3/19/2004 | 3/19/2004 12:00:00 AM | P | PART |
|
|
DAVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for extension of permit ok owner said he is going to secure contracor to take over job in the future 3/19/2004 3:19:18 PM
|