Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00699 FIRE-Final Inspection3/18/20043/19/20043/19/2004 12:00:00 AMAFAIL
Shell fire sprinkler system forward flush test failed. 3/19/2004 9:33:58 AM
BLD04-00041 FIRE-Final Inspection3/18/20043/19/20043/19/2004 12:00:00 AMAFAIL
Shell fire sprinkler system forward flush test failed. 3/19/2004 9:34:04 AM
BLD04-00042 FIRE-Final Inspection3/18/20043/19/20043/19/2004 12:00:00 AMAFAIL
Shell fire sprinkler system forward flush test failed. 3/19/2004 9:34:10 AM
BLD03-02407 FIRE-Final Inspection3/18/20043/19/20043/19/2004 12:00:00 AMAFAIL
Provide and test duct smoke detectors per IMC. Provide the correct remote leds. Paint curbing. Provide"door to remain unlocked during business hours" sticker. Provide approved door hardware on pocket doors and south facing exit door. Provide annual inspection for the fire extinguishers 3/19/2004 3:41:52 PM
FIR03-00224 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMACANC
To be rescheduled 3/19/2004 7:46:02 AM
FIR02-00022 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMACANC
To be rescheduled 3/19/2004 7:46:13 AM
FIR02-00499 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMACANC
To be rescheduled 3/19/2004 7:46:23 AM
FIR02-00273 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMAPASS
Underground finaled
FIR04-00104 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMAPASS
Fire alarms finaled. This inspection is for the shell/core portion only. This includes sprinkler monitoring and HVAC shut down. This permit was mistakenly attached to the TI permit should have been attached to BLD02-00699 which is the shell/core permit. per Troy C///3/19/04 BAM
FIR02-00499 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMACANC
To be rescheduled 3/19/2004 7:48:48 AM
FIR02-00499 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMACANC
To be rescheduled 3/19/2004 7:48:48 AM
FIR03-00108 INSP-Final Inspection3/17/20043/19/20043/19/2004 12:00:00 AMAFAIL
light switch under the hood does not shut down. Only the micro switch was tripped. Suppression system was not set off. 3/19/2004 9:36:13 AM
FIR03-00711 INSP-Final Inspection3/17/20043/19/20043/19/2004 12:00:00 AMAFAIL
I spoke with the owner and the manager about the existing hood. It is not code compliant so I went over some of the noncompliance issues. She stated that either a new hood would be installed or smaller appliances installed 3/19/2004 10:17:19 AM
FIR02-00499 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire alarm finaled 3/19/2004 1:34:44 PM
FIR02-00499 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPCANC
duplicate inspection 3/19/2004 1:34:33 PM
FIR03-00012 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPFAIL
Plans need to be resubmitted showing the new door magnet/security interface. Items tested today are both phone lines, vavle tamper switch and battery calculations which are ok. The smoke detector is now approved to be used with this panel. 3/19/2004 4:34:10 PM
FIR04-00040 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPFAIL
No devices tested. The remote alarm LED's for the duct smoke detectors did not operate 3/19/2004 4:06:17 PM
BLD02-00699 FIRE-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
Fire life safety finaled. The shell/core fire alarm permit (FIR04-00104) has been mistakenly attached to a tenant improvement permit. 3/19/2004 2:08:47 PM
BLD04-00042 FIRE-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire life safety finaled 3/19/2004 2:58:39 PM
FIR02-00347 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire sprinklers finaled
BLD01-03230 FIRE-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
Fire life safety, fire alarm and fire sprinklers finaled
FIR02-00435 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire alarm finaled
FIR04-00094 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire sprinkler finaled
FIR03-00224 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire alarm finaled 3/19/2004 1:33:36 PM
FIR02-00022 INSP-Final Inspection3/19/20043/19/20043/19/2004 12:00:00 AMPPASS
fire alarm finaled 3/19/2004 1:36:49 PM
BLD02-02452 FIRE-Final Inspection3/18/20043/19/20043/19/2004 12:00:00 AMPPASS
fire life safety finaled 3/19/2004 3:34:41 PM
FIR04-00158 INSP-Final Inspection3/18/20043/19/20043/18/2004 3:17:59 PMACANC
smick- ###-#### Disp set to [CANC] by a contractor via Hello! on Mar 18 2004 3:17PM.