Inspections for the day of: Monday, March 19, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-01010 INSP-Sprinkler Rough-in/Hydro3/19/20073/19/20073/20/2007 9:51:40 AMPPART
UG fire supply line hydrostatic test passed.
FIR07-00174 INSP-Sprinkler Rough-in3/16/20073/19/20073/20/2007 9:50:42 AMPFAIL
OH fire sprinkler piping is still completely concealed by insulation at the entire basement floor level, proper rough-in inspection cannot be completed until work is exposed.
FIR07-00102 INSP-Sprinkler Rough-in3/19/20073/19/20073/20/2007 9:47:38 AMPPART
Corrections have been verified for compliance of meeting min. required depth of bury for the UG supply line piping, installation is approved for cover.
FIR07-00179 INSP-Sprinkler Rough-in/Hydro3/18/20073/19/20073/19/2007 2:19:48 PMAPART
OH hydrostatic test passed inspection.
FIR06-00639 INSP-Sprinkler Rough-in/Hydro3/16/20073/19/20073/19/2007 1:08:25 PMAPART
Hydrostatic test of the OH main and standpipes completed satisfactory.
FIR07-00034 INSP-Sprinkler Rough-in/Hydro3/16/20073/19/20073/19/2007 12:17:55 PMADEFR
Inspection request intended for project related UG permit.
FIR07-00179 INSP-Final Inspection3/18/20073/19/20073/19/2007 11:23:17 AMAPART
OH rough-in is approved for cover, noted leaking 1/2" weld-o-let at the riser supply FLxGV piece, missing head box, outside bell, need ceilings and escutcheons and sprinkler supervision alarm testing prior to permit final.
FIR07-00179 INSP-Supply line flush3/18/20073/19/20073/19/2007 11:18:08 AMAPART
UG supply line flush completed.