BLD07-00013
| FIRE-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 7:02:23 PM | P | FAIL |
|
|
Inspection was for a conference on door hardware and fire extinguisher locations.
|
BLD07-00316
| FIRE-Alarm Testing | 3/18/2007 | 3/19/2007 | 3/19/2007 7:00:57 PM | P | PASS |
|
|
The duct detector tested worked correctly.
|
BLD06-03181
| FIRE-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 3:40:56 PM | P | FAIL |
|
|
Need to get the fire alarm permit finaled and test all of the emergency lights and exit signs.
|
FIR06-00874
| INSP-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 3:39:47 PM | P | PART |
|
|
Hydro test for the pre-action system passed. Hangers have been attached to the bottom chord of the trusses. An engineer needs to sign off on this or the hanger need to go to the top chord.
|
BLD06-03181
| FIRE-Final Inspection | 3/16/2007 | 3/19/2007 | 3/19/2007 2:35:30 PM | A | FAIL |
|
|
Need to get the fire alarm permit finaled and test all of the emergency lights and exit signs.
|
FIR07-00200
| INSP-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 2:30:17 PM | P | FAIL |
|
|
The west most duct smoke detector is oriented incorrectly in the vertical ducting. It will need to be relocated and tested prior to finaling this permit.
|
FIR07-00076
| INSP-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 2:25:08 PM | P | PASS |
|
|
Permit finaled
|
BLD05-00453
| FIRE-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 2:09:37 PM | P | PASS |
|
|
life safety passed
|
BLD05-00454
| FIRE-Final Inspection | 3/19/2007 | 3/19/2007 | 3/19/2007 2:09:09 PM | P | PASS |
|
|
life safety passed
|