Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00013 FIRE-Final Inspection3/19/20073/19/20073/19/2007 7:02:23 PMPFAIL
Inspection was for a conference on door hardware and fire extinguisher locations.
BLD07-00316 FIRE-Alarm Testing3/18/20073/19/20073/19/2007 7:00:57 PMPPASS
The duct detector tested worked correctly.
BLD06-03181 FIRE-Final Inspection3/19/20073/19/20073/19/2007 3:40:56 PMPFAIL
Need to get the fire alarm permit finaled and test all of the emergency lights and exit signs.
FIR06-00874 INSP-Final Inspection3/19/20073/19/20073/19/2007 3:39:47 PMPPART
Hydro test for the pre-action system passed. Hangers have been attached to the bottom chord of the trusses. An engineer needs to sign off on this or the hanger need to go to the top chord.
BLD06-03181 FIRE-Final Inspection3/16/20073/19/20073/19/2007 2:35:30 PMAFAIL
Need to get the fire alarm permit finaled and test all of the emergency lights and exit signs.
FIR07-00200 INSP-Final Inspection3/19/20073/19/20073/19/2007 2:30:17 PMPFAIL
The west most duct smoke detector is oriented incorrectly in the vertical ducting. It will need to be relocated and tested prior to finaling this permit.
FIR07-00076 INSP-Final Inspection3/19/20073/19/20073/19/2007 2:25:08 PMPPASS
Permit finaled
BLD05-00453 FIRE-Final Inspection3/19/20073/19/20073/19/2007 2:09:37 PMPPASS
life safety passed
BLD05-00454 FIRE-Final Inspection3/19/20073/19/20073/19/2007 2:09:09 PMPPASS
life safety passed