Inspections for the day of: Wednesday, March 19, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00649 Electrical Rough-In3/18/20083/19/20083/19/2008 3:11:44 PMPFAIL
240 volt recep is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten talked with owner he needs to remove the sink he installed below the panel
ELE08-00418 Final3/19/20083/19/20083/19/2008 2:28:38 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok core shell card signed
ELE07-03440 Final3/19/20083/19/20083/19/2008 2:28:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok core shell card signed
ELE08-00420 Final3/19/20083/19/20083/19/2008 2:27:45 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok core shell card signed
ELE08-00419 Final3/19/20083/19/20083/19/2008 2:27:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok core shell card signed
ELE08-00574 Permanent Service3/19/20083/19/20083/19/2008 12:51:39 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer p/s u/g new ok
ELE08-00644 Electrical Rough-In3/19/20083/19/20083/19/2008 11:53:21 AMPPASS
Eddie also a final? Phone #: ###-#### ok
ELE08-00644 Final3/19/20083/19/20083/19/2008 11:53:10 AMPPASS
Eddie also a final? Phone #: ###-#### ok
ELE08-00646 Electrical Rough-In3/18/20083/19/20083/19/2008 10:14:29 AMAPART
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL u/g ok
ELE08-00296 Electrical Rough-In3/18/20083/19/20083/19/2008 9:44:18 AMAPART
Scheduled by a contractor via Hello! on 3/18/2008 at 2:01:17 PM. Contact: ###-####. 2nd level of u/g ok
ELE08-00641 Permanent Service3/18/20083/19/20083/19/2008 9:08:15 AMAFAIL
Ready for service inspection so we can get IPCo connected. Then we will turn on power and determine what needs to be fixed. Phone #: ###-#### Internet Inspection Request from: Mick Williams corr called 312.5(C) exception ser not allowed in conduit, unless it exits the top, needs concrete encased electrode, 250.104(A)(1) bond water to service not sub panel, 110.3(A&B) use proper sized lugs or terminals for conductors250.142(B) 4 wire recepts and pigtails for range and dryer, 100.12(A) seal unused 2" top of sub panel
ELE08-00651 Temporary Service3/18/20083/19/20083/19/2008 8:07:49 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk t/s u/g new ok