Inspections for the day of: Wednesday, March 19, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02952 Final3/19/20083/19/20083/19/2008 4:21:04 PMPPASS
ok to final
ELE06-02762 Electrical Rough-In3/19/20083/19/20083/19/2008 3:38:29 PMPCANC
Partial rough-in inspection. Either A.M. or P.M. is fine. Pleae call Jim at ###-#### 10 minutes before arrival. I will provide access. Phone #: ###-#### Internet Inspection Request from: James Cornwell see conference
ELE06-02762 Conference3/19/20083/19/20083/19/2008 3:38:09 PMPDONE
Partial rough-in inspection. Either A.M. or P.M. is fine. Pleae call Jim at ###-#### 10 minutes before arrival. I will provide access. Phone #: ###-#### Internet Inspection Request from: James Cornwell reviewed make-up requirements, 1/14" for mc, nm, and ent, 6" free conductor, outlet spacing, low voltage grounding for distribution box
ELE08-00259 Final3/19/20083/19/20083/19/2008 3:08:11 PMPPASS
Eric Phone #: ###-#### ok to final
ELE07-03738 Final3/19/20083/19/20083/19/2008 2:25:32 PMPPASS
House will be opened from 12:30 to 4:30 Phone #: ###-#### Internet Inspection Request from: Roy Kay owners moved into bedrooms, could not check receptacles, rest ok, ok to final
ELE08-00562 Electrical Rough-In3/19/20083/19/20083/19/2008 1:29:39 PMPPASS
jeff Phone #: ###-#### ok to cover inside house only, will call back for concrete encased electrode
ELE08-00653 Temporary Service3/19/20083/19/20083/19/2008 12:41:54 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman t/s o/h n ok
ELE07-03958 Final3/18/20083/19/20083/19/2008 11:27:56 AMAPASS
rocky Phone #: ###-#### corrections made, ok to final
ELE07-02422 Conference3/17/20083/19/20083/19/2008 10:18:51 AMADONE
Perry ###-#### talked about service, subpanels, ground rods, wire bending radius, oversize lb, receptacles, feed subpanel back to back, pull box
ELE08-00493 Final3/17/20083/19/20083/19/2008 9:35:57 AMAPASS
re-inspection. front unit will be unlocked. tenant will be home in rear unit. Phone #: ###-#### Internet Inspection Request from: Carla Ward called contractor, corrections made, ok to final
ELE08-00549 Rough-In Permanent Service3/18/20083/19/20083/19/2008 9:12:34 AMAFAIL
justin Phone #: ###-#### called, left correction notice, BCC address shall be posted, job id sticker shall be posted, approved set of plans shall be on job, wiring shall be terminated in boxes, NEC 362.30(A) ent shall be securely fastened within 3' of box, 362.46 bushings or adapter shall be installed at box,334.30 nm cable shall be secured within 12" of box, 314.17 conductors entering boxes shall be protected from abrasion, 110.26(F)(2) no other equipment shall be located in dedicated space about electrical equipment-lv under meter
ELE08-00548 Rough-In Permanent Service3/18/20083/19/20083/19/2008 8:28:41 AMAFAIL
justin Phone #: ###-#### called left correction notice, BCC address shall be posted, job id sticker shall be posted, approved set of plans shall be on job, wiring shall be terminated in boxes, NEC 362.30(A) ent shall be securely fastened within 3' of box, 362.46 bushings or adapter shall be installed at box, 334.30 nm cable shall be secured within 12" of box, 314.17 conductors entering boxes shall be protected from abrasion, 110.26(F)(2) no other equipment shall be located in dedicated space about electrical equipment-lv under meter