ESC06-01207
| Aging Inspection | 3/19/2009 | 3/19/2009 | 3/20/2009 2:54:43 PM | | CANC |
|
|
|
ELE08-02423
| Electrical Rough-In | 3/19/2009 | 3/19/2009 | 3/19/2009 4:56:45 PM | P | PASS |
|
|
jason Phone #: ###-#### floor heat 1 bath rm bld#3, unit 101
|
ELE09-00346
| Final | 3/18/2009 | 3/19/2009 | 3/19/2009 4:14:35 PM | P | FAIL |
|
|
this is just a few exit lights and some minor code violation needed fixed. also there are two panels where the main switches are not grouped nothing has been done to that I know this is a violation but the owners dont believe things we tell them. just letting you know we are not trying to pull the wool over your eyes or that we are not aware of the nec. thanks don simpson Phone #: ###-#### Internet Inspection Request from: DONNY SIMPSON corr met electrician, shall provide labels for more than 1 service to bld 230.2 (D&E), BCC no violations retained, all grounding and bonding for service shall meet 2008 article 250, 400.7&8 shall remove all cord used as fixed wiring for djay lighting, 410.62(C) electric discharge fixtures shall use recept and cord cap, with recept above fixture, support jbox above p/s seal all unused breaker KOs
|
ELE09-00412
| Permanent Service | 3/12/2009 | 3/19/2009 | 3/19/2009 1:42:56 PM | P | PASS |
|
|
Mitch- call 30 mins prior to going Phone #: ###-#### p/s u/g rec. ok
|
ELE09-00444
| Electrical Rough-In | 3/18/2009 | 3/19/2009 | 3/19/2009 9:18:13 AM | A | PASS |
|
|
Brian Phone #: ###-#### kit remodel, called needs larger 2 gang right of sink for box fill contr will correct
|
ELE09-00431
| Rough-In Permanent Service | 3/18/2009 | 3/19/2009 | 3/19/2009 8:41:53 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas r/i p/s u/g new ok
|