Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00075 INSP-Sprinkler Rough-in3/19/20103/19/20103/22/2010 5:15:33 PMPPART
Underground fire supply line including the stub-in and riser piece are approved for cover.
FIR10-00094 INSP-Sprinkler Rough-in/Hydro3/18/20103/19/20103/22/2010 12:00:00 AMAPASS
Underground hydro and underground flush both passed inspection.
FIR09-00707 INSP-Sprinkler Rough-in3/18/20103/19/20103/19/2010 3:31:18 PMAPART
Pendent head at the locker room vestibule hard lid ceiling is okay for cover- see clouded area with today's date and initials on approved plan set sheet FP-4.
BLD09-02253 FIRE-Final Inspection3/18/20103/19/20103/19/2010 3:27:59 PMAPASS
Fire life safety passed inspection, two additional fire extinguishers posted while on site, discussed building upgrade agreement on file.
FIR09-00734 INSP-Final Inspection3/18/20103/19/20103/19/2010 3:24:48 PMAPASS
Remainder of items per latest inspection activity verified for completion, some issues addressed while on site, fire sprinkler permit okay for final.
FIR10-00049 INSP-Final Inspection3/17/20103/19/20103/19/2010 3:22:36 PMAPASS
Correction items revised, re-testing completed acceptable, as-builts recieved, fire alarm permit finaled.
BLD10-00103 FIRE-Final Inspection3/19/20103/19/20103/19/2010 1:43:49 PMPPASS
Fire life safety completed satisfactory, inspection passed.
FIR10-00110 INSP-Final Inspection3/19/20103/19/20103/19/2010 1:43:04 PMPPASS
Fire alarm permit approved for final status.
FIR10-00062 INSP-Final Inspection3/19/20103/19/20103/19/2010 1:41:58 PMPPASS
Fire sprinkler work passed final inspection, C/N items done, permit finaled.
FIR10-00110 INSP-Alarm Testing3/18/20103/19/20103/19/2010 1:39:54 PMAPASS
Fire alarm work passed field testing.
FIR10-00047 INSP-Sprinkler Rough-in3/18/20103/19/20103/19/2010 12:00:00 AMAFAIL
Jeremy Phone #: ###-####

Several upright sprinklers were painted and needed to be replaced.
Was unable to gain access to room 100 to verify the fire protection.
Room 103, the storage was to close to the sprinkler and obstructed the coverage. I notify a tenant representative of the obstruction problem.