FIR10-00075
| INSP-Sprinkler Rough-in | 3/19/2010 | 3/19/2010 | 3/22/2010 5:15:33 PM | P | PART |
|
|
Underground fire supply line including the stub-in and riser piece are approved for cover.
|
FIR10-00094
| INSP-Sprinkler Rough-in/Hydro | 3/18/2010 | 3/19/2010 | 3/22/2010 12:00:00 AM | A | PASS |
|
|
Underground hydro and underground flush both passed inspection.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 3/18/2010 | 3/19/2010 | 3/19/2010 3:31:18 PM | A | PART |
|
|
Pendent head at the locker room vestibule hard lid ceiling is okay for cover- see clouded area with today's date and initials on approved plan set sheet FP-4.
|
BLD09-02253
| FIRE-Final Inspection | 3/18/2010 | 3/19/2010 | 3/19/2010 3:27:59 PM | A | PASS |
|
|
Fire life safety passed inspection, two additional fire extinguishers posted while on site, discussed building upgrade agreement on file.
|
FIR09-00734
| INSP-Final Inspection | 3/18/2010 | 3/19/2010 | 3/19/2010 3:24:48 PM | A | PASS |
|
|
Remainder of items per latest inspection activity verified for completion, some issues addressed while on site, fire sprinkler permit okay for final.
|
FIR10-00049
| INSP-Final Inspection | 3/17/2010 | 3/19/2010 | 3/19/2010 3:22:36 PM | A | PASS |
|
|
Correction items revised, re-testing completed acceptable, as-builts recieved, fire alarm permit finaled.
|
BLD10-00103
| FIRE-Final Inspection | 3/19/2010 | 3/19/2010 | 3/19/2010 1:43:49 PM | P | PASS |
|
|
Fire life safety completed satisfactory, inspection passed.
|
FIR10-00110
| INSP-Final Inspection | 3/19/2010 | 3/19/2010 | 3/19/2010 1:43:04 PM | P | PASS |
|
|
Fire alarm permit approved for final status.
|
FIR10-00062
| INSP-Final Inspection | 3/19/2010 | 3/19/2010 | 3/19/2010 1:41:58 PM | P | PASS |
|
|
Fire sprinkler work passed final inspection, C/N items done, permit finaled.
|
FIR10-00110
| INSP-Alarm Testing | 3/18/2010 | 3/19/2010 | 3/19/2010 1:39:54 PM | A | PASS |
|
|
Fire alarm work passed field testing.
|
FIR10-00047
| INSP-Sprinkler Rough-in | 3/18/2010 | 3/19/2010 | 3/19/2010 12:00:00 AM | A | FAIL |
|
|
Jeremy Phone #: ###-####
Several upright sprinklers were painted and needed to be replaced.
Was unable to gain access to room 100 to verify the fire protection.
Room 103, the storage was to close to the sprinkler and obstructed the coverage. I notify a tenant representative of the obstruction problem.
|