Inspections for the day of: Tuesday, March 19, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02700 ELE-Aging Inspection3/19/20133/19/20133/19/2013 3:31:31 PM DONE
have called contractor, waiting for call for final
ELE13-00124 Final3/19/20133/19/20133/19/2013 2:44:21 PMPPASS
Garage entrance code 1968E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE13-00534 Permanent Service3/19/20133/19/20133/19/2013 2:01:28 PMPPASS
I had to move the meter base. Needs to be restickered.The Phone #: ###-#### >> Inspection requested via web by Bob Glenn p/s u/g n ok
ELE13-00435 Electrical Rough-In3/19/20133/19/20133/19/2013 12:55:47 PMPPASS
Need a ceiling inspection. Contact Fabian for any questions. Phone #: ###-#### >> Inspection requested via web by Tina Payne ok cover ceiling
ELE13-00358 Electrical Rough-In3/18/20133/19/20133/19/2013 10:46:39 AMAPASS
Contact is Phil Bassack - NOTE: THIS INSPECTION IS TO REVIEW U.L. LISTINGS OF EQUIPMENT FURNISHED PER REQUEST FROM BOB REICHERT Phone #: ###-#### >> Inspection requested via web by Scott Campbell saw equipment listings for heads and contactor boxes
ELE13-00638 Electrical Rough-In3/19/20133/19/20133/19/2013 10:45:16 AMPPASS
Tony Phone #: ###-#### work done without permit until today, left correction notice 2-27-13 stating to get permit, could only see wiring in receptacles, general contractor pulled electrical permit, he said electrician did work, told contractor to provide circuit directory and provide work space around panel, ri ok, see final
ELE13-00638 Final3/19/20133/19/20133/19/2013 10:44:59 AMAPASS
Tony Phone #: ###-#### ok final
ELE13-00631 Rough-In Permanent Service3/18/20133/19/20133/19/2013 9:54:35 AMACANC
Trench cover Phone #: ###-#### >> Inspection requested via web by David Seilheimer see ri
ELE13-00631 Electrical Rough-In3/19/20133/19/20133/19/2013 9:36:19 AMAPASS
Trench cover Phone #: ###-#### >> Inspection requested via web by David Seilheimer ok cover trench, check for schedule 80 riser
ELE13-00592 Electrical Rough-In3/18/20133/19/20133/19/2013 9:32:34 AMAPASS
pool and spa bonding--UG cover Phone #: ###-#### >> Inspection requested via web by Kevin Koomler pool and spa bond ok, u/g ok cover
ELE13-00611 Temporary Service3/18/20133/19/20133/19/2013 9:11:15 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE13-00333 Final3/19/20133/19/20133/19/2013 8:49:39 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe ok final
ELE13-00610 Rough-In Permanent Service3/18/20133/19/20133/19/2013 8:40:12 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, left correction notice, NEC 314.17(C) nm cable shall be stapled within 8" of box, 300.4(A)(1) shall add nailplates if edge of bored hole is less than 1 1/4" from face of framing member, 210.52 shall add receptacle in wall over 2', BCC shall add box for bath light, shall not cover any wiring prior to inspection- foam in holes