FIR13-00713
| INSP-Sprinkler Rough-in | 3/19/2014 | 3/19/2014 | 3/19/2014 5:17:54 PM | P | PART |
|
|
Verified corrections and adjustments at the first floor only. Overspaced hangers at two locations not yet complete. Noted possible light fixture obstructions due to proximity of junction boxes to heads at some locations-
|
FIR14-00034
| INSP-Final Inspection | 3/19/2014 | 3/19/2014 | 3/19/2014 5:08:51 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR14-00122
| INSP-Final Inspection | 3/19/2014 | 3/19/2014 | 3/19/2014 5:07:57 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR13-00677
| INSP-Final Inspection | 3/19/2014 | 3/19/2014 | 3/19/2014 1:03:36 PM | A | PASS |
|
|
Remainder of the scope of work completed. Final walkthrough passed. Fire sprinkler permit finaled.
|
BLD13-02790
| FIRE-Final Inspection | 3/18/2014 | 3/19/2014 | 3/19/2014 1:01:44 PM | A | PASS |
|
|
Life safety inspection completed. Need to remove the manual thumbturn at the main entry/exit and replace with a key operated device prior to structural final as discussed.
|
BLD11-02367
| FIRE-Final Inspection | 3/18/2014 | 3/19/2014 | 3/19/2014 12:58:09 PM | A | PASS |
|
|
Verified previous correction items. Life safety finaled.
|
BLD13-02788
| FIRE-Final Inspection | 3/18/2014 | 3/19/2014 | 3/19/2014 12:55:32 PM | A | FAIL |
|
|
Items noted include; repair exit signs at the basement level, provide approved hardware at the main entry/exit doors, the fire sprinkler system is overdue annual certification.
|
BLD13-00181
| FIRE-Conference | 3/19/2014 | 3/19/2014 | | P | |
|
|
JC at phone #: ###-####
|