Inspections for the day of: Thursday, March 19, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01385 ELE-Aging Inspection3/19/20153/19/20153/24/2015 4:00:13 PM DONE
mitch said he would try to contact homeowners
ELE14-03316 Electrical Rough-In3/18/20153/19/20153/19/2015 2:57:41 PMPPASS
Contact Tom hartung for garage roof rough in raceways. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on deck parking garage ceiling (see Tom's new concrete pour plans -pink area today)
ELE15-00629 Electrical Rough-In3/12/20153/19/20153/19/2015 2:17:01 PMPFAIL
Shane Phone #: ###-#### 334.30-nm cable shall be supported and secured within 12 " of box and every 41/2 feet. 300.4(A)(1)-where a cable is ran thru bored holes, no more than 11/4" from hole to face of stud. 210.52(A)(1)-receptacles shall be installed so that no point measured horizontally along the floorline of any wall space is more than 6 foot from a recetacle. 250.53(2)-a single ground rod shall be supplemented by an additional ground rod.
ELE15-00055 Electrical Rough-In3/19/20153/19/20153/19/2015 1:03:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton light pole bases and signs pole bases and u.ground conduits r/i ok
ELE15-00670 Final3/18/20153/19/20153/19/2015 12:03:22 PMAPASS
Darrell-please contact 30 min prior Phone #: ###-#### final ok
ELE15-00139 Permanent Service3/18/20153/19/20153/19/2015 11:31:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Clint Tate corrections made p/s u/g n ok
ELE14-03333 Electrical Rough-In3/19/20153/19/20153/19/2015 11:05:21 AMAPASS
CONTACT: JEREMY THORNOCK Phone #: ###-#### Inspection requested via web by Deb Gooden r/i ok level 2 wing 3 rms. interior and exterior. 9 pole bases ok to pour
ELE14-03336 Electrical Rough-In3/19/20153/19/20153/19/2015 9:33:47 AMAPASS
CONTACT: JEREMY THORNOCK Phone #: ###-#### Inspection requested via web by Deb Gooden r/i 2nd flr wing 1 interior rooms ok see e sheets
ELE15-00196 Electrical Rough-In3/18/20153/19/20153/19/2015 8:14:07 AMAPASS
We are requesting a ceiling inspection for tomorrow 3/19/15 in the AM. Our onsite contact is Rod @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate r/i t bar ceiling ok
ELE15-02131 Electrical Rough-In3/19/20153/19/20153/19/2015 12:00:00 AMAPASS
Rough-in inspection 2nd floor units west wing. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok 2nd level west wing see E2.1