ELE12-01385
| ELE-Aging Inspection | 3/19/2015 | 3/19/2015 | 3/24/2015 4:00:13 PM | | DONE |
|
|
mitch said he would try to contact homeowners
|
ELE14-03316
| Electrical Rough-In | 3/18/2015 | 3/19/2015 | 3/19/2015 2:57:41 PM | P | PASS |
|
|
Contact Tom hartung for garage roof rough in raceways. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok slab on deck parking garage ceiling (see Tom's new concrete pour plans -pink area today)
|
ELE15-00629
| Electrical Rough-In | 3/12/2015 | 3/19/2015 | 3/19/2015 2:17:01 PM | P | FAIL |
|
|
Shane Phone #: ###-#### 334.30-nm cable shall be supported and secured within 12 " of box and every 41/2 feet. 300.4(A)(1)-where a cable is ran thru bored holes, no more than 11/4" from hole to face of stud. 210.52(A)(1)-receptacles shall be installed so that no point measured horizontally along the floorline of any wall space is more than 6 foot from a recetacle. 250.53(2)-a single ground rod shall be supplemented by an additional ground rod.
|
ELE15-00055
| Electrical Rough-In | 3/19/2015 | 3/19/2015 | 3/19/2015 1:03:39 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton light pole bases and signs pole bases and u.ground conduits r/i ok
|
ELE15-00670
| Final | 3/18/2015 | 3/19/2015 | 3/19/2015 12:03:22 PM | A | PASS |
|
|
Darrell-please contact 30 min prior Phone #: ###-#### final ok
|
ELE15-00139
| Permanent Service | 3/18/2015 | 3/19/2015 | 3/19/2015 11:31:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Clint Tate corrections made p/s u/g n ok
|
ELE14-03333
| Electrical Rough-In | 3/19/2015 | 3/19/2015 | 3/19/2015 11:05:21 AM | A | PASS |
|
|
CONTACT: JEREMY THORNOCK Phone #: ###-#### Inspection requested via web by Deb Gooden r/i ok level 2 wing 3 rms. interior and exterior. 9 pole bases ok to pour
|
ELE14-03336
| Electrical Rough-In | 3/19/2015 | 3/19/2015 | 3/19/2015 9:33:47 AM | A | PASS |
|
|
CONTACT: JEREMY THORNOCK Phone #: ###-#### Inspection requested via web by Deb Gooden r/i 2nd flr wing 1 interior rooms ok see e sheets
|
ELE15-00196
| Electrical Rough-In | 3/18/2015 | 3/19/2015 | 3/19/2015 8:14:07 AM | A | PASS |
|
|
We are requesting a ceiling inspection for tomorrow 3/19/15 in the AM. Our onsite contact is Rod @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate r/i t bar ceiling ok
|
ELE15-02131
| Electrical Rough-In | 3/19/2015 | 3/19/2015 | 3/19/2015 12:00:00 AM | A | PASS |
|
|
Rough-in inspection 2nd floor units west wing. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok 2nd level west wing see E2.1
|