Inspections for the day of: Monday, March 19, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03023 FIRE-Conference3/16/20183/19/20183/19/2018 3:27:16 PMPDONE
Matt and I discussed filling the spaces under the main platform and the audio/visual control area. We also discussed the apparent need for a manual fire alarm system as based on the review comments and the occupant load/fire alarm requirements in the IFC for an A-3 occupancy.


Matt Phone #: ###-####
FIR17-00447 INSP-Sprinkler Rough-in/Hydro3/19/20183/19/20183/19/2018 2:28:37 PMPPASS
Overhead hydro test passed
BLD17-03339 FIRE-Final Inspection3/16/20183/19/20183/19/2018 2:28:01 PMPFAIL
Remove the dead bolt on the door between dining and the playland area and also install an exit sign as per the plans, mount the fire extinguisher in the Playland area, repair the two emergency lights in the Kitchen area and finish installing the exit discharge light out the back Kitchen door, install the Occupant Load signs (two). The hood suppression and fire extinguishers are current with inspections.

Justin Phone #: ###-####
FIR18-00189 INSP-Final Inspection3/19/20183/19/20183/19/2018 1:03:43 PMPPASS
Permit finaled
FIR17-00441 INSP-Sprinkler Rough-in3/19/20183/19/20183/19/2018 12:58:34 PMPPASS
Rough-in and tenting passed. Piping can be covered.
FIR17-00450 INSP-Sprinkler Rough-in3/19/20183/19/20183/19/2018 12:56:20 PMPPASS
Rough-in and tenting passed. Piping can be covered.
FIR18-00129 INSP-Conference3/19/20183/19/20183/19/2018 12:54:49 PMPDONE
Leroy and I discussed the hangers. Per Scott Arellano the hangers need to meet code, whether it be current or the code under which they were originally installed.
BLD17-01548 FIRE-Final Inspection3/16/20183/19/20183/19/2018 10:55:30 AMAPART
A temporary for life safety is being given with Assistant Chief Ron's permission until the two pre-action systems/rooms have been addressed. Per the contractor the smoke detectors are active in these rooms. They will need to remain active until the associated pre-action system is functional.
FIR18-00093 INSP-Sprinkler Rough-in/Hydro3/16/20183/19/20183/19/2018 10:04:53 AMACANC
Duplicate inspection

rick Phone #: ###-####
FIR18-00093 INSP-Sprinkler Rough-in3/16/20183/19/20183/19/2018 10:04:30 AMAPASS
The piping above the hardlids is ok to cover except the three Kitchen areas which are not complete yet.
BLD14-03139 FIRE-Final Inspection3/16/20183/19/20183/19/2018 8:32:20 AMAPASS
life safety passed

Greg Phone #: ###-####
FIR18-00025 INSP-Sprinkler Rough-in3/16/20183/19/20183/19/2018 7:33:17 AMAPASS
Rough-in passed. Piping is ok to cover.