BLD17-03023
| FIRE-Conference | 3/16/2018 | 3/19/2018 | 3/19/2018 3:27:16 PM | P | DONE |
|
|
Matt and I discussed filling the spaces under the main platform and the audio/visual control area. We also discussed the apparent need for a manual fire alarm system as based on the review comments and the occupant load/fire alarm requirements in the IFC for an A-3 occupancy.
Matt Phone #: ###-####
|
FIR17-00447
| INSP-Sprinkler Rough-in/Hydro | 3/19/2018 | 3/19/2018 | 3/19/2018 2:28:37 PM | P | PASS |
|
|
Overhead hydro test passed
|
BLD17-03339
| FIRE-Final Inspection | 3/16/2018 | 3/19/2018 | 3/19/2018 2:28:01 PM | P | FAIL |
|
|
Remove the dead bolt on the door between dining and the playland area and also install an exit sign as per the plans, mount the fire extinguisher in the Playland area, repair the two emergency lights in the Kitchen area and finish installing the exit discharge light out the back Kitchen door, install the Occupant Load signs (two). The hood suppression and fire extinguishers are current with inspections.
Justin Phone #: ###-####
|
FIR18-00189
| INSP-Final Inspection | 3/19/2018 | 3/19/2018 | 3/19/2018 1:03:43 PM | P | PASS |
|
|
Permit finaled
|
FIR17-00441
| INSP-Sprinkler Rough-in | 3/19/2018 | 3/19/2018 | 3/19/2018 12:58:34 PM | P | PASS |
|
|
Rough-in and tenting passed. Piping can be covered.
|
FIR17-00450
| INSP-Sprinkler Rough-in | 3/19/2018 | 3/19/2018 | 3/19/2018 12:56:20 PM | P | PASS |
|
|
Rough-in and tenting passed. Piping can be covered.
|
FIR18-00129
| INSP-Conference | 3/19/2018 | 3/19/2018 | 3/19/2018 12:54:49 PM | P | DONE |
|
|
Leroy and I discussed the hangers. Per Scott Arellano the hangers need to meet code, whether it be current or the code under which they were originally installed.
|
BLD17-01548
| FIRE-Final Inspection | 3/16/2018 | 3/19/2018 | 3/19/2018 10:55:30 AM | A | PART |
|
|
A temporary for life safety is being given with Assistant Chief Ron's permission until the two pre-action systems/rooms have been addressed. Per the contractor the smoke detectors are active in these rooms. They will need to remain active until the associated pre-action system is functional.
|
FIR18-00093
| INSP-Sprinkler Rough-in/Hydro | 3/16/2018 | 3/19/2018 | 3/19/2018 10:04:53 AM | A | CANC |
|
|
Duplicate inspection
rick Phone #: ###-####
|
FIR18-00093
| INSP-Sprinkler Rough-in | 3/16/2018 | 3/19/2018 | 3/19/2018 10:04:30 AM | A | PASS |
|
|
The piping above the hardlids is ok to cover except the three Kitchen areas which are not complete yet.
|
BLD14-03139
| FIRE-Final Inspection | 3/16/2018 | 3/19/2018 | 3/19/2018 8:32:20 AM | A | PASS |
|
|
life safety passed
Greg Phone #: ###-####
|
FIR18-00025
| INSP-Sprinkler Rough-in | 3/16/2018 | 3/19/2018 | 3/19/2018 7:33:17 AM | A | PASS |
|
|
Rough-in passed. Piping is ok to cover.
|