Inspections for the day of: Thursday, March 19, 2020.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00943 Final3/19/20203/19/20203/19/2020 3:46:28 PMPFAIL
Meet Jasper on site. Repairs as per your request have been made.

Jasper - ###-#### - Please give him 30 minutes notice so he can meet you there. Thanks! Phone #: ###-####
Inspection requested via web by Ted Dumont Inc.
- A/C still needs fuses
- line set insulation needs repaired at indoor coil
MEC20-01083 Final3/18/20203/19/20203/19/2020 3:08:37 PMPPASS
Please call when on way: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC20-01163 Final3/18/20203/19/20203/19/2020 2:48:47 PMPNR
Please precall Josh to ensure ready for inspection. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
MEC20-01162 Pressure Test3/18/20203/19/20203/19/2020 2:41:09 PMPCANC
Please inspect later PM and call Chuck on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC20-01162 Final3/19/20203/19/20203/19/2020 2:41:02 PMPPASS
Please inspect later PM and call Chuck on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace ac coil co ok
MEC20-00940 Rough-in3/19/20203/19/20203/19/2020 1:50:18 PMPPASS
Mechanical Gas Fireplace Rough-In Inspection Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace R/I ok
MEC20-01106 Final3/16/20203/19/20203/19/2020 1:36:40 PMPFAIL
95% furnace replaced. Phone #: ###-#### Inspection requested via web by Brian Preece
- need to witness a 5lb flue pressure test
MEC20-01133 Rough-in3/18/20203/19/20203/19/2020 1:00:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- b vent still needs replaced
MEC20-01086 Pressure Test3/18/20203/19/20203/19/2020 11:14:55 AMAFAIL
Kyle Phone #: ###-####
- underground gas line needs 18 gauge tracer wire installed DO NOT BACKFILL
- gas line penetrations needs protective coating applied
- need to see a R/I inspection on line set/ condensate line inside walls and ceiling of house
MEC20-01169 Rough-in3/18/20203/19/20203/19/2020 10:44:58 AMAPASS
Call 1/2 hour prior to meet you there Phone #: ###-#### Inspection requested via web by Rene Neumeyer
-fireplace R/I ok
MEC20-01169 Pressure Test3/18/20203/19/20203/19/2020 10:43:29 AMAPASS
Call 1/2 hour prior to meet you there Phone #: ###-#### Inspection requested via web by Rene Neumeyer
-20lb gas pressure test
MEC20-00946 Final3/18/20203/19/20203/19/2020 9:48:32 AMAPASS
Please call Robert prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC20-01040 Rough-in3/18/20203/19/20203/19/2020 9:15:32 AMAFAIL
corrections made for rough-in inspection Phone #: ###-#### Inspection requested via web by Carlene Badillo
- 5lb flue pressure test fail
MEC20-01040 Pressure Test3/18/20203/19/20203/19/2020 9:15:08 AMAFAIL
corrections made, ready to re-test vent Phone #: ###-#### Inspection requested via web by Carlene Badillo
- 5lb flue pressure test fail gauge was flat
MEC20-00626 Final3/18/20203/19/20203/19/2020 9:01:24 AMAPASS
Please call Nicole prior to arrival to ensure available at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace ac coil co ok
MEC20-00943 Final3/18/20203/19/20203/19/2020 8:42:33 AMAFAIL
Please contact Jasper 30 minutes prior to your arrival so he could meet you on site. If he misses your call please contact us at ###-####. Phone #: ###-#### Inspection requested via web by Ted Dumont Inc.
- A/C needs 35 amp max fuses
- b vent needs 1" clearances in attic and garage
- insulation shield in garage and attic roof lines
- line set and condensate line penetration needs sealed
- line set insulation at indoor unit needs repaired
MEC19-03816 Mec-Aging Inspection3/19/20203/19/20203/19/2020 8:11:43 AM FAIL
Permit has not been active since passing a pressure test on 8-27-19. Schedule a final inspection with owner if work is done. Permit will expire at next mechanical aging inspection if not active.