ELE05-00590
| Final | 3/1/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | A | PASS |
|
|
Corrections have been completed.Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 3/2/2005 9:01:56 AM
|
ELE04-03939
| Electrical Rough-In | 3/1/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | A | PART |
|
|
THIS IS FOR A SERVICE INSPECTION. ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok 3/2/2005 9:50:35 AM
|
ELE05-00637
| Electrical Rough-In | 3/1/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 3/1/2005 at 9:32:34 AM. Contact: ###-####. 4 walls in big rm 3/2/2005 10:15:16 AM
|
ELE05-00661
| Conference | 3/1/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | A | DONE |
|
|
rex --###-#### ok 3/2/2005 8:28:18 AM
|
ELE04-03939
| Permanent Service | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE05-00558
| Electrical Rough-In | 3/1/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | FAIL |
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted met owner 300.14 free length, 300.4 (A)(1)&(D), 310.15 derate wires in nipple over 24", 110.14 needs device for splices and use listed devices listed when mixing copper and alum 3/2/2005 4:58:09 PM
|
ELE05-00672
| Rough-In Permanent Service | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | FAIL |
|
|
bill-- ###-#### cor. posted called 300.4, 250.122 use # 12 for grd pigtail 3 gang switch back door, 250.52(A)(1) 104(A)(1) grd or bond p/s old house water system 210.52(A) address outlet spacing old part of house where spacing changed because of new opening, uncover all u/g install by excavation contractor, have electrical contractor install it and call for inspection, also have approved plans at job site 3/2/2005 2:00:06 PM
|
ELE05-00646
| Temporary Service | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | FAIL |
|
|
###-#### darrin no address and grd rod shall be flush with grade called 3/2/2005 12:03:07 PM
|
ELE05-00059
| Final | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | PART |
|
|
Ready for partial final, please contact Steve, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters t/o for kitchen , break area ok 3/2/2005 2:47:51 PM
|
ELE05-00481
| Final | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | NR |
|
|
Ready for final, please contact Steve, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters correction posted to office equipment people,406.4 recepts not secure in office furniture assembly, and recepts shall project 0.015 in. from steel faceplates 3/2/2005 2:53:16 PM
|
ELE05-00643
| Temporary Service | 3/2/2005 | 3/2/2005 | 3/2/2005 12:00:00 AM | P | PASS |
|
|
Roger; Phone #: ###-#### Internet Inspection Request from: Jan Rice t/s o/h new ok 3/2/2005 3:59:22 PM
|