Inspections for the day of: Wednesday, March 2, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00665 Temporary Service3/1/20053/2/20053/2/2005 12:00:00 AMAPASS
kathy ###-#### t/s u/g n ok 3/2/2005 7:30:06 AM
ELE05-00668 Temporary Service3/1/20053/2/20053/2/2005 12:00:00 AMAFAIL
Kim; Phone #: ###-#### Internet Inspection Request from: Jan Rice 406.4(D) recpt shall project from faceplate, 406.8(B)(2) recpt shall use in-use cover, 310.12(C) ungrounded conductors shall not be white, BCC job id sticker shall be posted. Re-nspection fee due. called contr , left corr notice. 3/2/2005 10:16:57 AM
ELE05-00300 Final3/2/20053/2/20053/2/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called contr about check garage gfci and a/c fuses. ok to final 3/2/2005 9:33:21 AM
ELE05-00299 Final3/2/20053/2/20053/2/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called contr about 2 recpts and panel labels. ok to final 3/2/2005 9:53:49 AM
ELE04-04114 Final3/1/20053/2/20053/2/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/1/2005 at 2:37:58 PM. Contact: ###-####. called contr,358.6 emt fittings shall be listed, 314.15(A) wet locations shall be listed for wet locations, 225.22 raceways shall be raintight in wet locations, left corr notice 3/2/2005 8:52:02 AM
ELE05-00447 Final3/2/20053/2/20053/2/2005 12:00:00 AMAFAIL
358.6 emt fittings shall be listed, 314.15(A) wet locations shall be listed for use in wet locations, 225.22 raceways shall be raintight in wet locations, called contr, left corr notice
ELE03-01485 Final3/1/20053/2/20053/2/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/1/2005 at 10:01:27 AM. Contact: ###-####. hot tub was installed, but has been removed and all wiring disconnected. ok to final 3/2/2005 4:25:00 PM
ELE05-00523 Electrical Rough-In3/1/20053/2/20053/2/2005 12:00:00 AMPFAIL
Robert; Phone #: ###-#### Internet Inspection Request from: Jan Rice 300.4(D) nm cable shall be 1 1/4" from edge, 314.17(C) nm shall be fastened within 8" of box, BCC all r/i shall be done, shall supply boxes for outside recpts and lighting, left corr. notice, told son 3/2/2005 1:35:16 PM
ELE05-00669 Rough-In Permanent Service3/2/20053/2/20053/2/2005 12:00:00 AMPPASS
leon ###-#### called contr and said they have to have app. plans on job. ric ok p/s u/g n ok 3/2/2005 2:05:33 PM
ELE05-00045 Final3/2/20053/2/20053/2/2005 12:00:00 AMPPASS
rundle electric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore people have all furniture moved into new addition. Able to check 90% of outlets. rest ok, ok to final . Called contractor to verify that he was done and not doing rest of remodel work in exst bath. 3/2/2005 3:45:59 PM
ELE04-02821 Final3/2/20053/2/20053/2/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/2/2005 at 8:33:20 AM. Contact: ###-####. ok to final. contr there and will put on covers in 2 plcs. finishing out door lite. 3/2/2005 1:00:45 PM