ELE06-00730
| Rough-In Permanent Service | 3/2/2006 | 3/2/2006 | 3/2/2006 1:57:53 PM | P | PASS |
|
|
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g new ok
|
ELE06-00729
| Rough-In Permanent Service | 3/2/2006 | 3/2/2006 | 3/2/2006 1:55:54 PM | P | PASS |
|
|
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g new ok
|
ELE06-00720
| Rough-In Permanent Service | 3/2/2006 | 3/2/2006 | 3/2/2006 12:38:21 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr. called 210.52(A) outlet spacing 5 locations see marks on floor, 314.29 jtub box shall be accessible
|
ELE05-03636
| Final | 3/1/2006 | 3/2/2006 | 3/2/2006 11:34:47 AM | A | NR |
|
|
STEVE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called need info
|
ELE06-00697
| Final | 3/1/2006 | 3/2/2006 | 3/2/2006 9:28:48 AM | A | FAIL |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. not made 110.26 clearence for p/s, 250.8 no SMS zinsco subpanel, also reove white grd wire attached to panel,310.16 needs breaker for subpanel in laundry rm 408.4 label all panels, 408.38 needs cover and dead front zinsco subpanel fee due
|
ELE06-00715
| Electrical Rough-In | 3/1/2006 | 3/2/2006 | 3/2/2006 8:19:56 AM | A | PASS |
|
|
###-#### - Note: also detached garage ok
|
ELE06-00715
| Rough-In Permanent Service | 3/1/2006 | 3/2/2006 | 3/2/2006 8:19:18 AM | A | PASS |
|
|
###-#### r/i p/s o/h new ok
|