Inspections for the day of: Thursday, March 2, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00730 Rough-In Permanent Service3/2/20063/2/20063/2/2006 1:57:53 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
r/i p/s u/g new ok
ELE06-00729 Rough-In Permanent Service3/2/20063/2/20063/2/2006 1:55:54 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
r/i p/s u/g new ok
ELE06-00720 Rough-In Permanent Service3/2/20063/2/20063/2/2006 12:38:21 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr. called 210.52(A) outlet spacing 5 locations see marks on floor, 314.29 jtub box shall be accessible
ELE05-03636 Final3/1/20063/2/20063/2/2006 11:34:47 AMANR
STEVE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called need info
ELE06-00697 Final3/1/20063/2/20063/2/2006 9:28:48 AMAFAIL
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. not made 110.26 clearence for p/s, 250.8 no SMS zinsco subpanel, also reove white grd wire attached to panel,310.16 needs breaker for subpanel in laundry rm 408.4 label all panels, 408.38 needs cover and dead front zinsco subpanel fee due
ELE06-00715 Electrical Rough-In3/1/20063/2/20063/2/2006 8:19:56 AMAPASS
###-#### - Note: also detached garage ok
ELE06-00715 Rough-In Permanent Service3/1/20063/2/20063/2/2006 8:19:18 AMAPASS
###-#### r/i p/s o/h new ok