FIR05-00659
| INSP-Sprinkler Rough-in/Hydro | 3/2/2006 | 3/2/2006 | 3/3/2006 1:27:50 PM | P | DEFR |
|
|
Inspection to be scheduled for 3/3 as discussed with contractor.
|
BLD01-01632
| FIRE-Final Inspection | 3/1/2006 | 3/2/2006 | 3/3/2006 1:26:56 PM | A | CANC |
|
|
No time to perform this inspection today, to be rescheduled.
|
FIR06-00122
| INSP-Final Inspection | 3/2/2006 | 3/2/2006 | 3/3/2006 12:53:54 PM | P | CANC |
|
|
No time for this inspection today, to be rescheduled per conversation with contractor for 3/3.
|
FIR06-00035
| INSP-Final Inspection | 3/1/2006 | 3/2/2006 | 3/2/2006 5:50:39 PM | P | FAIL |
|
|
The sample tubes in one duct are incorrectly oriented, one AHU is non-functional and thus cannot be tested at this time, av's and EOL tested okay.
|
BLD05-03100
| FIRE-Final Inspection | 3/2/2006 | 3/2/2006 | 3/2/2006 3:57:57 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00615
| INSP-Final Inspection | 2/27/2006 | 3/2/2006 | 3/2/2006 3:14:27 PM | A | PASS |
|
|
Fire alarm is acceptable for final.
|
FIR05-00611
| INSP-Final Inspection | 2/28/2006 | 3/2/2006 | 3/2/2006 3:13:21 PM | A | FAIL |
|
|
Fire sprinkler must meet requirements of NFPA 13 2002 7.3.2.4 (3) with respect to the installation of pendent sprinklers on preaction systems.
|
FIR05-00610
| INSP-Alarm Testing | 2/28/2006 | 3/2/2006 | 3/2/2006 3:07:36 PM | A | FAIL |
|
|
Visual notification devices within the remodeled area are not in sync as required, vesda tested okay, door release is functional, one heat detector remains to be tested.
|
BLD05-02620
| FIRE-Final Inspection | 2/27/2006 | 3/2/2006 | 3/2/2006 3:02:24 PM | A | NR |
|
|
The project related alarm and sprinkler permits must pass inspection prior to life safety final approval.
|
MIS06-00041
| FIR-Final | 2/27/2006 | 3/2/2006 | 3/2/2006 3:00:18 PM | A | FAIL |
|
|
Remove manual thumbturns at the main entry/exit door and the door from warehouse area, keyed locking hardware is allowed at the main entry/exit with signage above the door, cover open electrical boxes and secure loose/unused wire, provide fire extinguishers as discussed for the office and warehouse areas, provide building address.
|
FIR05-00456
| INSP-Final Inspection | 2/27/2006 | 3/2/2006 | 3/2/2006 1:20:10 PM | A | PASS |
|
|
Fire alarm passed inspection.
|
FIR05-00807
| INSP-Final Inspection | 3/1/2006 | 3/2/2006 | 3/2/2006 1:17:14 PM | A | PASS |
|
|
Requested corrections have been made, fire alarm tested satisfactory.
|
FIR06-00126
| INSP-Sprinkler Rough-in | 3/1/2006 | 3/2/2006 | 3/2/2006 9:36:47 AM | A | PART |
|
|
Inspected thrust block at 90, ductile stub-in, tracer wire, and NRS valve for PI, good for cover at these areas, street connection is not complete at this time, need retaining method at riser flange.
|