FIR06-00562
| FIR-Aging Inspection | 3/2/2007 | 3/2/2007 | 3/5/2007 1:17:29 PM | | DONE |
|
|
wip
|
FIR06-00667
| INSP-Final Inspection | 3/1/2007 | 3/2/2007 | 3/5/2007 10:48:55 AM | P | FAIL |
|
|
Manual pull stations included in the scope of work must also meet current code requirements, noted missing SD at the new NAC panel.
|
FIR07-00167
| INSP-Final Inspection | 3/1/2007 | 3/2/2007 | 3/5/2007 10:46:29 AM | P | PASS |
|
|
Fire alarm modifications passed field inspection, permit finaled.
|
FIR06-00696
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:59:50 PM | P | PASS |
|
|
Demo permitted work finaled.
|
FIR06-00550
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:59:05 PM | P | PASS |
|
|
UG fire supply line permit finaled.
|
FIR05-00659
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:58:14 PM | P | PASS |
|
|
Items on correction notices field verified for compliance, fire sprinkler permit finaled.
|
FIR05-00620
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:56:12 PM | P | PASS |
|
|
UG supply line permit finaled, resubmitted and approved under FIR05-00659.
|
FIR05-00397
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:54:30 PM | P | PASS |
|
|
Demo permit finaled.
|
FIR07-00109
| INSP-Final Inspection | 3/2/2007 | 3/2/2007 | 3/2/2007 3:52:05 PM | A | PASS |
|
|
Fire alarm test passed field inspection, permit finaled.
|
FIR06-00073
| INSP-Final Inspection | 2/27/2007 | 3/2/2007 | 3/2/2007 2:01:29 PM | P | PASS |
|
|
Final fire sprinkler inspection passed, flow switch delay adjusted while on site, permit finaled.
|
FIR06-00893
| INSP-Final Inspection | 3/1/2007 | 3/2/2007 | 3/2/2007 2:00:17 PM | A | FAIL |
|
|
Panel must be programed to provide non-latching supervisory signals for sprinkler tamper switches as required, also need to clear knox box trouble at the panel prior to final. Remainder of alarm work passed inspection.
|
FIR06-00073
| INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 3/2/2007 | 3/2/2007 1:54:52 PM | A | PART |
|
|
OH hydrostatic test passed. The OH rough-in installation is satisfactory, noted missing test orfice at remote inspectors test connection.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 3/1/2007 | 3/2/2007 | 3/2/2007 12:26:29 PM | A | PART |
|
|
OH rough-in for the 5th floor SE TI area is okay for cover as noted, need to relocate two overspaced heads at the atrium glass, install head in the janitors closet, repair fireproofing at some hanger locations where removed.
|
MIS07-00035
| FIR-Final | 3/1/2007 | 3/2/2007 | 3/2/2007 10:20:12 AM | A | PASS |
|
|
Items on c/n verified for compliance, life safety inspection passed.
|
FIR06-00595
| INSP-Alarm Testing | 3/1/2007 | 3/2/2007 | 3/2/2007 10:16:44 AM | A | PART |
|
|
Alarm testing for the 4th floor SE and SW quads only-retest of the av's passed but will need to add missing notification in conference room 4SE, manual pulls and SD at the SE tested okay , noted address # at the panel do not match two SD at the SW quad exit door and service elevator, also noted two non-functional SD in the SW telephone room and electrical room. Also tested av notification devices on the 2nd floor skybridges.
|
FIR06-00967
| INSP-Final Inspection | 3/1/2007 | 3/2/2007 | 3/2/2007 8:47:00 AM | P | CANC |
|
|
AFTER 2:30, let me know when you can be there... Phone #: ###-#### Inspection cancelled from web by: Rick Groom
|