Inspections for the day of: Friday, March 2, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00562 FIR-Aging Inspection3/2/20073/2/20073/5/2007 1:17:29 PM DONE
wip
FIR06-00667 INSP-Final Inspection3/1/20073/2/20073/5/2007 10:48:55 AMPFAIL
Manual pull stations included in the scope of work must also meet current code requirements, noted missing SD at the new NAC panel.
FIR07-00167 INSP-Final Inspection3/1/20073/2/20073/5/2007 10:46:29 AMPPASS
Fire alarm modifications passed field inspection, permit finaled.
FIR06-00696 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:59:50 PMPPASS
Demo permitted work finaled.
FIR06-00550 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:59:05 PMPPASS
UG fire supply line permit finaled.
FIR05-00659 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:58:14 PMPPASS
Items on correction notices field verified for compliance, fire sprinkler permit finaled.
FIR05-00620 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:56:12 PMPPASS
UG supply line permit finaled, resubmitted and approved under FIR05-00659.
FIR05-00397 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:54:30 PMPPASS
Demo permit finaled.
FIR07-00109 INSP-Final Inspection3/2/20073/2/20073/2/2007 3:52:05 PMAPASS
Fire alarm test passed field inspection, permit finaled.
FIR06-00073 INSP-Final Inspection2/27/20073/2/20073/2/2007 2:01:29 PMPPASS
Final fire sprinkler inspection passed, flow switch delay adjusted while on site, permit finaled.
FIR06-00893 INSP-Final Inspection3/1/20073/2/20073/2/2007 2:00:17 PMAFAIL
Panel must be programed to provide non-latching supervisory signals for sprinkler tamper switches as required, also need to clear knox box trouble at the panel prior to final. Remainder of alarm work passed inspection.
FIR06-00073 INSP-Sprinkler Rough-in/Hydro2/27/20073/2/20073/2/2007 1:54:52 PMAPART
OH hydrostatic test passed. The OH rough-in installation is satisfactory, noted missing test orfice at remote inspectors test connection.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro3/1/20073/2/20073/2/2007 12:26:29 PMAPART
OH rough-in for the 5th floor SE TI area is okay for cover as noted, need to relocate two overspaced heads at the atrium glass, install head in the janitors closet, repair fireproofing at some hanger locations where removed.
MIS07-00035 FIR-Final3/1/20073/2/20073/2/2007 10:20:12 AMAPASS
Items on c/n verified for compliance, life safety inspection passed.
FIR06-00595 INSP-Alarm Testing3/1/20073/2/20073/2/2007 10:16:44 AMAPART
Alarm testing for the 4th floor SE and SW quads only-retest of the av's passed but will need to add missing notification in conference room 4SE, manual pulls and SD at the SE tested okay , noted address # at the panel do not match two SD at the SW quad exit door and service elevator, also noted two non-functional SD in the SW telephone room and electrical room. Also tested av notification devices on the 2nd floor skybridges.
FIR06-00967 INSP-Final Inspection3/1/20073/2/20073/2/2007 8:47:00 AMPCANC
AFTER 2:30, let me know when you can be there... Phone #: ###-#### Inspection cancelled from web by: Rick Groom