Inspections for the day of: Friday, March 2, 2007.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00601 INSP-Sprinkler Rough-in/Hydro3/2/20073/2/20073/5/2007 1:39:02 PMPPASS
Above ground hydro test passed.
FIR05-00536 INSP-Sprinkler Rough-in3/1/20073/2/20073/2/2007 4:23:07 PMPPASS
See the city approved plans for the piping above the 5th floor hardlids that is ok to cover.
FIR07-00096 INSP-Final Inspection3/1/20073/2/20073/2/2007 4:21:49 PMPCANC
To be rescheduled for next friday.
BLD06-03452 FIRE-Final Inspection3/1/20073/2/20073/2/2007 3:25:22 PMPPASS
Life safety finaled
BLD06-03452 FIRE-Final Inspection3/1/20073/2/20073/2/2007 3:08:13 PMAPASS
life safety passed
FIR07-00110 INSP-Final Inspection3/1/20073/2/20073/2/2007 3:04:52 PMAPASS
permit finaled
FIR06-00924 INSP-Final Inspection3/2/20073/2/20073/2/2007 2:18:47 PMPPASS
permit finaled
FIR06-00874 INSP-Sprinkler Rough-in/Hydro3/1/20073/2/20073/2/2007 2:06:46 PMAFAIL
Above ground hydro test failed.
FIR06-00922 INSP-Final Inspection3/2/20073/2/20073/2/2007 2:04:43 PMPPASS
permit finaled
BLD06-03109 FIRE-Final Inspection3/1/20073/2/20073/2/2007 1:12:07 PMPPASS
Life safety passed.
BLD06-03109 FIRE-Alarm Testing3/1/20073/2/20073/2/2007 1:11:30 PMPPASS
Fire alarm has been tested and passed.
FIR07-00084 INSP-Final Inspection3/1/20073/2/20073/2/2007 12:19:58 PMPPASS
Permit finaled
BLD05-03196 FIRE-Final Inspection3/1/20073/2/20073/2/2007 11:45:06 AMPPASS
life safety passed
BLD06-01803 FIRE-Final Inspection3/1/20073/2/20073/2/2007 11:03:09 AMAPASS
life safety finaled
FIR06-00585 INSP-Final Inspection3/1/20073/2/20073/2/2007 10:55:34 AMAPASS
permit finaled
FIR06-00466 INSP-Final Inspection3/1/20073/2/20073/2/2007 10:25:25 AMAFAIL
The items tested today were three duct smoke detectors. Mike Timmerman accompanied me on this inspection and verified that additional strobes will be required in the stock rooms due to blockage by the racks. Mike and I also pointed out overspacing of strobes in the retail area.
FIR06-00958 INSP-Sprinkler Rough-in/Hydro3/1/20073/2/20073/2/2007 10:17:44 AMAPASS
Underground supply and the remote FDC piping is ok to cover from the stub out to 15' past the patio
FIR06-00515 INSP-Final Inspection3/1/20073/2/20073/2/2007 9:42:58 AMACANC
FIre alarm was not ready so this inspection could not be completed.
FIR06-00641 INSP-Sprinkler Rough-in/Hydro3/1/20073/2/20073/2/2007 9:42:13 AMAPART
Lower area sprinkler piping is ok to cover. Need to remove the plywood from the trusses as discussed. Doghouse area has not been inspected yet.
BLD06-02534 FIRE-Final Inspection3/1/20073/2/20073/2/2007 9:41:01 AMAFAIL
Need to get the sprinkler permit and fire alarm permits finaled first. No inspection performed.
BLD06-00212 FIRE-Final Inspection3/1/20073/2/20073/2/2007 9:40:28 AMAFAIL
Need to get the sprinkler permit and fire alarm permits finaled first. No inspection performed.
FIR06-00913 INSP-Final Inspection3/1/20073/2/20073/2/2007 9:39:33 AMAFAIL
Need shell system finaled first and it failed. Reason is Need to resubmit plans showing the added expansion board in the fire alarm panel. There are seven new zones. Only items tested were the phone lines and phone line #1 failed at first because it was not programed correctly.
FIR06-00804 INSP-Final Inspection3/1/20073/2/20073/2/2007 9:38:25 AMAFAIL
Need to resubmit plans showing the added expansion board in the fire alarm panel. There are seven new zones. Only items tested were the phone lines and phone line #1 failed at first because it was not programed correctly.
FIR06-00585 INSP-Alarm Testing3/1/20073/2/20073/1/2007 12:00:00 AMADONE
Phone #: ###-####