Inspections for the day of: Monday, March 2, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02905 Final3/2/20093/2/20093/2/2009 3:36:12 PMPPART
Please provide partial final inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean t/o card signed for all areas anop
ELE09-00260 Permanent Service2/27/20093/2/20093/2/2009 1:44:17 PMPPART
Scheduled by a contractor via Hello! on 2/27/2009 at 7:16:05 AM. conference only ok
ELE09-00260 Electrical Rough-In2/27/20093/2/20093/2/2009 1:43:28 PMPFAIL
Scheduled by a contractor via Hello! on 2/27/2009 at 7:14:04 AM. Contact: ###-####. replace 2 gang boxes that are damaged, 110.3(A), shall not use 2 big conn. back of panel for cables 312.5, addoutlets for wall space, 210.52(A), nail plates and 11/4" 300.4, 250.48 grd metal boxes , 314.16 check box fill
ELE07-02945 Final3/2/20093/2/20093/2/2009 12:03:54 PMPPASS
wes Phone #: ###-#### survey 210.8 gfci all recepts final ok
ELE08-02167 Permanent Service2/27/20093/2/20093/2/2009 9:51:05 AMAPASS
andy Phone #: ###-#### needs 3/0 for GEC and bonds p/s u/g new ok
ELE09-00325 Permanent Service2/27/20093/2/20093/2/2009 8:31:37 AMAPASS
inspection to turn on service//Kim ###-#### p/s u/g rec. ok
ELE09-00325 Final3/2/20093/2/20093/2/2009 8:31:10 AMAPASS
inspection to turn on service//Kim ###-#### ok