Inspections for the day of: Wednesday, March 2, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00569 INSP-Conference3/2/20113/2/20113/3/2011 5:01:00 PMPDONE
Site visit regarding suspended light fixture placement at the east side main level. Upright sprinkler protection does not appear obstructed as currently installed.
BLD11-00032 FIRE-Final Inspection3/2/20113/2/20113/2/2011 4:30:05 PMPPASS
Fire life safety passed with the exception of surface mounted hasps and locks at the west and south exit doors to be removed prior to occpancy as discussed.
FIR11-00091 INSP-Final Inspection3/2/20113/2/20113/2/2011 4:27:27 PMPPASS
Scope of fire sprinkler work passed inspection. Permit finaled.
BLD10-01525 FIRE-Sprinkler Rough-in3/2/20113/2/20113/2/2011 4:26:12 PMPPART
Okay to cover overhead fire sprinkler modifications at the drop ceilings.
FIR10-00006 INSP-Final Inspection2/18/20113/2/20113/2/2011 4:24:24 PMAPART
Tested fire alarm notification and initiating devices on the 2nd -7th floor tower levels, verified previous correction items are finished, booster 2 nac 3 first floor is not functional, add TS at the antifreeze loop to the points map, adjust cd and spacing at area D 2nd and 3rd floors as noted.
BLD11-00062 FIRE-Final Inspection3/2/20113/2/20113/2/2011 4:19:00 PMAPART
Door hardware and fire sprinkler work has been finished. Final pending alarm system permit work.
BLD10-02344 FIRE-Final Inspection3/2/20113/2/20113/2/2011 4:17:05 PMAPASS
Fire life safety finaled.
BLD10-02879 FIRE-Final Inspection3/1/20113/2/20113/2/2011 4:12:54 PMAFAIL
New walls have created spacing and obstruction issues with the existing fire sprinkler and alarm systems. Modifications to maintain and continue protection will be necessary via approved FIR permit work-