ELE11-00295
| ELE-Aging Inspection | 3/2/2012 | 3/2/2012 | 3/6/2012 7:09:04 AM | | DONE |
|
|
wsuc
|
ELE12-00114
| Conference | 3/2/2012 | 3/2/2012 | 3/2/2012 2:59:38 PM | P | DONE |
|
|
called contractor about cord feed fixtures , note they were installed by owner no permit told contr to tell to remove them , contr will then wire them and call for final
|
ELE11-01168
| Final | 3/2/2012 | 3/2/2012 | 3/2/2012 2:57:21 PM | P | PASS |
|
|
sign
|
ELE12-00445
| Electrical Rough-In | 3/2/2012 | 3/2/2012 | 3/2/2012 2:57:11 PM | P | PASS |
|
|
mike Phone #: ###-####
|
ELE12-00390
| Electrical Rough-In | 3/2/2012 | 3/2/2012 | 3/2/2012 1:26:40 PM | P | NR |
|
|
Ryan Phone #: ###-#### jbox ok no splicing not done , also needs to grd or bond water system from new p/s not jbox and shall use #4 copper see 250.52(A)(1), for GEC or 250.104(A)(1) if bonding water pipes sized to table 250.66
|
ELE12-00443
| Electrical Rough-In | 3/1/2012 | 3/2/2012 | 3/2/2012 11:38:18 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin
|
ELE12-00170
| Electrical Rough-In | 2/28/2012 | 3/2/2012 | 3/2/2012 11:38:01 AM | A | PART |
|
|
bryan Phone #: ###-#### note ceiling only J-tbs not listed, 2 reccess fixtures in MB not airtight
|
ELE12-00435
| Electrical Rough-In | 3/1/2012 | 3/2/2012 | 3/2/2012 11:34:05 AM | A | PART |
|
|
Need underground inspection....Mike Clover ###-#### Phone #: ###-#### >> Inspection requested via web by Kevin Perez u/g ok
|
ELE12-00431
| Electrical Rough-In | 3/1/2012 | 3/2/2012 | 3/2/2012 8:43:38 AM | A | PASS |
|
|
back wall ok
|