Inspections for the day of: Friday, March 2, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00295 ELE-Aging Inspection3/2/20123/2/20123/6/2012 7:09:04 AM DONE
wsuc
ELE12-00114 Conference3/2/20123/2/20123/2/2012 2:59:38 PMPDONE
called contractor about cord feed fixtures , note they were installed by owner no permit told contr to tell to remove them , contr will then wire them and call for final
ELE11-01168 Final3/2/20123/2/20123/2/2012 2:57:21 PMPPASS
sign
ELE12-00445 Electrical Rough-In3/2/20123/2/20123/2/2012 2:57:11 PMPPASS
mike Phone #: ###-####
ELE12-00390 Electrical Rough-In3/2/20123/2/20123/2/2012 1:26:40 PMPNR
Ryan Phone #: ###-#### jbox ok no splicing not done , also needs to grd or bond water system from new p/s not jbox and shall use #4 copper see 250.52(A)(1), for GEC or 250.104(A)(1) if bonding water pipes sized to table 250.66
ELE12-00443 Electrical Rough-In3/1/20123/2/20123/2/2012 11:38:18 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin
ELE12-00170 Electrical Rough-In2/28/20123/2/20123/2/2012 11:38:01 AMAPART
bryan Phone #: ###-#### note ceiling only
J-tbs not listed, 2 reccess fixtures in MB not airtight
ELE12-00435 Electrical Rough-In3/1/20123/2/20123/2/2012 11:34:05 AMAPART
Need underground inspection....Mike Clover ###-#### Phone #: ###-#### >> Inspection requested via web by Kevin Perez u/g ok
ELE12-00431 Electrical Rough-In3/1/20123/2/20123/2/2012 8:43:38 AMAPASS
back wall ok