BLD11-01395
| FIRE-Final Inspection | 3/2/2012 | 3/2/2012 | 3/2/2012 5:06:19 PM | P | NR |
|
|
Missing two exit signs, post building address, delayed egress hardware is not yet installed. Discussed general fire life safety requirements.
|
FIR11-00431
| INSP-Sprinkler Rough-in/Hydro | 3/2/2012 | 3/2/2012 | 3/2/2012 5:04:13 PM | P | NR |
|
|
Deluge valve installation incomplete at this time. Main and branchline including drops in place. Two drops in need of adjustment.
|
FIR11-00575
| INSP-Alarm Testing | 2/29/2012 | 3/2/2012 | 3/2/2012 4:56:04 PM | P | PART |
|
|
Completed initial walkthrough and partial testing for fire alarm work at sector 30 and sector 40 sub fab mechanical areas. Notification appliances and pull stations tested okay. Noted address needs assigned at the sw stair MP and accurate descriptor provided for the nw MP. Notification coverage in the fabrication areas may become obstructed as more process equipment is installed. Discussed associated permits for tool monitoring, vesdas, added tamper switches. Elevator control functions are incomplete at this time.
|
FIR12-00074
| INSP-Final Inspection | 3/2/2012 | 3/2/2012 | 3/2/2012 3:06:26 PM | P | PASS |
|
|
Scope of fire alarm work passed field inspection. Permit finaled.
|
FIR11-00691
| INSP-Final Inspection | 3/1/2012 | 3/2/2012 | 3/2/2012 3:04:50 PM | A | DEFR |
|
|
Overbooked
|
FIR11-00563
| INSP-Sprinkler Rough-in/Hydro | 3/2/2012 | 3/2/2012 | 3/2/2012 3:02:00 PM | A | PART |
|
|
Overhead installation at the 1st floor mechanical room 162, corridor 2A, and electrical 159 okay for cover with the agreement changes in pipe routing at room 162 are approved. Also inspected 2nd floor units 221 thru 224, internet cafe and barber 270. Noted missing coverage at the storage closet in the barber room. See plans for annotations.
|
FIR11-00178
| FIR-Aging Inspection | 3/2/2012 | 3/2/2012 | 3/2/2012 1:15:03 PM | | DONE |
|
|
Ref. permit activity notes 2/1
|
FIR11-00216
| FIR-Aging Inspection | 3/2/2012 | 3/2/2012 | 3/2/2012 12:30:47 PM | | FAIL |
|
|
Need contractor final inspection request.
|
BLD12-00245
| FIRE-Final Inspection | 3/1/2012 | 3/2/2012 | 3/2/2012 12:22:31 PM | A | PASS |
|
|
Correction items field verified. Life safety passed.
|
FIR11-00527
| INSP-Final Inspection | 3/2/2012 | 3/2/2012 | 3/2/2012 12:19:01 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD12-00331
| FIRE-Final Inspection | 3/1/2012 | 3/2/2012 | 3/2/2012 12:18:18 PM | A | PASS |
|
|
Life safety approved pending door hardware at the main entry/exit (door knob to be removed) Replace with lever style as discussed- to be completed prior to structural final as agreed.
|
BLD12-00333
| FIRE-Final Inspection | 3/1/2012 | 3/2/2012 | 3/2/2012 12:13:17 PM | A | PASS |
|
|
Fire life safety inspection completed. Tenant to post max. occupant sign at "81" per correction notice and item #10 on the list of general requirements attatched to the permit documents. Remainder of items okayed.
|
FIR12-00112
| INSP-Sprinkler Rough-in | 3/1/2012 | 3/2/2012 | 3/2/2012 12:10:26 PM | A | PART |
|
|
Overhead work at the remodel area above and below ceilings approved for cover. Note: sheetrock divider adjacent to to the new restroom above storage room to be removed to facilitate upright coverage, annual system inspection is one month past due, missing coverage below existing overhead garage door.
|