Inspections for the day of: Monday, March 2, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01478 ELE-Aging Inspection3/2/20153/2/20153/10/2015 6:20:25 AM DONE
still under construction
ELE15-00534 Permanent Service3/2/20153/2/20153/2/2015 2:34:03 PMPPASS
Please contact Geoff Hannaford ###-#### for instructions. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce p/s o/h rec ok
ELE15-00283 Final3/2/20153/2/20153/2/2015 2:10:09 PMPPASS
Please call before going there Phone #: ###-#### Inspection requested via web by Chris Chesnut ok final, called contractor to advise the bld is for vanilla only, signed card
ELE14-01066 Electrical Rough-In3/2/20153/2/20153/2/2015 2:07:49 PMPPASS
Rough-in inspection walls H Commons rooms H01 - H30, remaining walls are block. Building permit number BLD13-00184. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok as requested
ELE14-01814 Electrical Rough-In3/2/20153/2/20153/2/2015 2:06:17 PMPPASS
Rough-in IL area ''C'' 1st floor hard lid ceilings rooms: C151-C154, C156, C157, and C158. Building permit number BLD13-00182. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
ELE14-02362 Temporary Service3/2/20153/2/20153/2/2015 1:32:38 PMPCANC
We are requesting a temp. occupancy inspection for this afternoon. Our onsite contact is Luke Hardy @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate see final
ELE14-02362 Final3/2/20153/2/20153/2/2015 1:32:10 PMPPART
We are requesting a temp. occupancy inspection for this afternoon. Our onsite contact is Luke Hardy @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate partial final ok,shall finish panel schedules and elevator, signed t/o card
ELE15-00472 Rough-In Permanent Service2/26/20153/2/20153/2/2015 11:27:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk called , ri ok, p/s u/g n ok
ELE15-00467 Rough-In Permanent Service2/27/20153/2/20153/2/2015 11:10:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE15-00530 Rough-In Permanent Service3/1/20153/2/20153/2/2015 11:08:22 AMAPASS
Phone #: ###-#### Inspection requested via web by HZ ZAHIC ri ok, p/s u/g n ok
ELE14-02462 Final2/27/20153/2/20153/2/2015 9:55:45 AMAFAIL
Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence called, left message, left correction notice, BCC 50% energy efficient bulbs shall be installed, 4-05-23 shall inspect depth of raceway to garage, 110.26 shall provide 3' clearance in front of panel, 250.32B shall not connect grounding electrode to grounded conductor, 250.66 shall provide 2 grounding electrodes at garage
ELE14-02463 Final2/27/20153/2/20153/2/2015 9:23:26 AMAFAIL
Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence called, left correction notice, BCC 50% lamps shall be energy efficient, NEC 110.26 shall provide 3' clear space in front of panel, 250.56 sahll provide 2 ground rods at garage, 410.16 shall provide 12" from edge of luminaire in masrter bedroom to edge of shelf
ELE14-03126 Electrical Rough-In2/27/20153/2/20153/2/2015 8:00:09 AMAPASS
UG ROUGH IN Phone #: ###-#### Inspection requested via web by JENNY EMEL u/g ok per conversation, front and rear building, gave general green sticker