Inspections for the day of: Wednesday, March 2, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00618 Permanent Service3/1/20163/2/20163/2/2016 2:55:27 PMAPASS
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER p/s o/h rec ok
ELE16-00434 Permanent Service3/2/20163/2/20163/2/2016 2:39:47 PMPPASS
would like call ahead; Wes Phone #: ###-#### Didcussed if AFCI is required. Informed that if no new wiring being done AFCI not needed for existing bedrooms. Found dissimilar metals in contact at slice points in old panel location 110.14. Grounded type receptacles on ungrounded circuits 406.4(D). No code violation shall be retained. p/s o/h rec ok
ELE15-03396 Permanent Service3/2/20163/2/20163/2/2016 2:16:36 PMPPASS
Inspection requested via web by Stacie Tasker p/s u/g n ok
ELE16-00621 Electrical Rough-In3/2/20163/2/20163/2/2016 1:38:51 PMPPART
Scott. Wall cover inspection. Phone #: ###-#### Inspection requested via web by Sean DeLacy
2 dividing walls with 1 yet to build, turning each room into 2 seperate offices. 2 walls rough in ok cover
ELE16-00234 Electrical Rough-In3/2/20163/2/20163/2/2016 12:49:59 PMPPASS
We need a ceiling cover inspection. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Grid rough in ok cover
ELE15-03117 Electrical Rough-In3/2/20163/2/20163/2/2016 12:18:08 PMPPASS
ceiling Inspection, Greg Millburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Grid complete. Rough in ok cover
ELE15-04130 Final3/1/20163/2/20163/2/2016 11:18:56 AMAFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt
210.8- All bathroom receptacle outlets shall have GFCI protection. Stool.
210.52(C)(5) ex- Peninsular counter receptacle outlet shall not be located more than 6" back from edge of over hang.
406.4(D)(2)- Grounded type receptacle outlets installed on ungrounded circuit shall have GFCI protection or be changed to ungrounded type receptacle.
408.4- Circuit directory shall be completed.
ELE16-00589 Rough-In Permanent Service3/2/20163/2/20163/2/2016 10:34:11 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
Rough in ok cover p/s u/g n ok
ELE16-00620 Rough-In Permanent Service3/1/20163/2/20163/2/2016 9:58:14 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
Rough in ok cover p/s u/g n ok
ELE16-00634 Temporary Service3/1/20163/2/20163/2/2016 9:16:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-00636 Temporary Service3/1/20163/2/20163/2/2016 9:08:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-00635 Temporary Service3/1/20163/2/20163/2/2016 9:03:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-00637 Temporary Service3/1/20163/2/20163/2/2016 8:50:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok