ELE16-00618
| Permanent Service | 3/1/2016 | 3/2/2016 | 3/2/2016 2:55:27 PM | A | PASS |
|
|
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER p/s o/h rec ok
|
ELE16-00434
| Permanent Service | 3/2/2016 | 3/2/2016 | 3/2/2016 2:39:47 PM | P | PASS |
|
|
would like call ahead; Wes Phone #: ###-#### Didcussed if AFCI is required. Informed that if no new wiring being done AFCI not needed for existing bedrooms. Found dissimilar metals in contact at slice points in old panel location 110.14. Grounded type receptacles on ungrounded circuits 406.4(D). No code violation shall be retained. p/s o/h rec ok
|
ELE15-03396
| Permanent Service | 3/2/2016 | 3/2/2016 | 3/2/2016 2:16:36 PM | P | PASS |
|
|
Inspection requested via web by Stacie Tasker p/s u/g n ok
|
ELE16-00621
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 1:38:51 PM | P | PART |
|
|
Scott. Wall cover inspection. Phone #: ###-#### Inspection requested via web by Sean DeLacy 2 dividing walls with 1 yet to build, turning each room into 2 seperate offices. 2 walls rough in ok cover
|
ELE16-00234
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 12:49:59 PM | P | PASS |
|
|
We need a ceiling cover inspection. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins Grid rough in ok cover
|
ELE15-03117
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 12:18:08 PM | P | PASS |
|
|
ceiling Inspection, Greg Millburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Grid complete. Rough in ok cover
|
ELE15-04130
| Final | 3/1/2016 | 3/2/2016 | 3/2/2016 11:18:56 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 210.8- All bathroom receptacle outlets shall have GFCI protection. Stool. 210.52(C)(5) ex- Peninsular counter receptacle outlet shall not be located more than 6" back from edge of over hang. 406.4(D)(2)- Grounded type receptacle outlets installed on ungrounded circuit shall have GFCI protection or be changed to ungrounded type receptacle. 408.4- Circuit directory shall be completed.
|
ELE16-00589
| Rough-In Permanent Service | 3/2/2016 | 3/2/2016 | 3/2/2016 10:34:11 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
ELE16-00620
| Rough-In Permanent Service | 3/1/2016 | 3/2/2016 | 3/2/2016 9:58:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
ELE16-00634
| Temporary Service | 3/1/2016 | 3/2/2016 | 3/2/2016 9:16:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE16-00636
| Temporary Service | 3/1/2016 | 3/2/2016 | 3/2/2016 9:08:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE16-00635
| Temporary Service | 3/1/2016 | 3/2/2016 | 3/2/2016 9:03:23 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE16-00637
| Temporary Service | 3/1/2016 | 3/2/2016 | 3/2/2016 8:50:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|