ELE16-00303
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 4:12:14 PM | P | PASS |
|
|
Rough in cover inspection. Catch up on inspection binder Phone #: ###-#### Inspection requested via web by Toby Groves Just update ESI binder no r/i insp.
|
ELE15-00495
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 4:10:28 PM | P | PASS |
|
|
Rough in for cover and catch up on inspection binder. Phone #: ###-#### Inspection requested via web by Toby Groves r/i walls ok level 4 thru 8 IT rooms and everything marked in green in ESI binder 1/4 size prints
|
ELE16-00412
| Final | 3/1/2016 | 3/2/2016 | 3/2/2016 1:27:41 PM | P | PASS |
|
|
final on lighting retrofit Phone #: ###-#### Inspection requested via web by Tim Dunlop final ok
|
ELE16-00644
| Electrical Rough-In | 3/1/2016 | 3/2/2016 | 3/2/2016 1:13:21 PM | P | PASS |
|
|
rough in will be ready for afternoon cover inspection and we''ll change the service one day this week thanks Phone #: ###-#### Inspection requested via web by Brad Baker r/i ok
|
ELE16-00642
| Conference | 3/1/2016 | 3/2/2016 | 3/2/2016 11:53:18 AM | A | DONE |
|
|
Pre-construction Conference with Rick Corn. Phone #: ###-#### Inspection requested via web by Cathy Duchek discuss tapping off 1400 amp main buss to feed new 800 amp chiller disco. ok if article 240.21 is followed.
|
ELE16-00623
| Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 9:16:17 AM | A | PASS |
|
|
Please call Jeff if you have any questions. Thanks Phone #: ###-#### Inspection requested via web by Brandon Blackham r/i walls ok
|
ELE16-00165
| Final | 3/1/2016 | 3/2/2016 | 3/2/2016 8:58:54 AM | A | PASS |
|
|
Call Scott 30 min before arrival ###-#### Phone #: ###-#### Inspection requested via web by danny perrine corrections made final ok
|
ELE16-00475
| Final | 3/1/2016 | 3/2/2016 | 3/2/2016 8:35:23 AM | A | PASS |
|
|
Final for permanent service. David Joseph is your contact ###-####. If you have any questions give him a call as he may not be on site. Phone #: ###-#### Inspection requested via web by Laura Longshaw final ok
|
ELE15-03882
| Electrical Rough-In | 3/1/2016 | 3/2/2016 | 3/2/2016 8:19:32 AM | A | PASS |
|
|
Garage Phone #: ###-#### Inspection requested via web by danny perrine r/i garage wiring and loadcenter ok
|