FIR16-00105
| INSP-Sprinkler Rough-in | 3/1/2016 | 3/2/2016 | 3/2/2016 3:12:15 PM | P | PASS |
|
|
Remaining underground piping is ok to cover. The initial portion of the piping was installed by United Water. Shilo has provided a letter assuming responcibility
|
FIR16-00055
| INSP-Final Inspection | 2/26/2016 | 3/2/2016 | 3/2/2016 2:45:46 PM | P | FAIL |
|
|
There were no city approved plans on site. I noted two devices in the Lobby area that do not match the plans provided. No test performed.
|
FIR16-00020
| INSP-Final Inspection | 2/29/2016 | 3/2/2016 | 3/2/2016 1:50:04 PM | P | FAIL |
|
|
Since the elevator contractor did not show up we could not get acces to the last heat detector to be tested in the elevator pit.
|
BLD15-02730
| FIRE-Final Inspection | 3/1/2016 | 3/2/2016 | 3/2/2016 1:48:44 PM | P | FAIL |
|
|
Need the project related fire alarm permit finaled, remove the exit sign directing people to the elevator, repair the non-functional exit signs/emergency lights, provide additional signage for the elevator on the second floor.
|
BLD15-04449
| FIRE-Final Inspection | 3/1/2016 | 3/2/2016 | 3/2/2016 10:53:38 AM | A | FAIL |
|
|
All items have been corrected except that a FIR permit is needed for the sprinkler head change out. When the FIR permit is finaled the life safety can be finaled.
|
BLD15-04039
| FIRE-Final Inspection | 3/2/2016 | 3/2/2016 | 3/2/2016 9:32:12 AM | P | PASS |
|
|
Life safety passed. Per owner, she contacted Carl in plan review and only the door hardware for the Activity Room needs to be ADA (has not been installed yet).
|
BLD16-00317
| FIRE-Final Inspection | 3/1/2016 | 3/2/2016 | 3/2/2016 8:44:55 AM | A | PASS |
|
|
Life safety passed
|
FIR16-00096
| INSP-Sprinkler Rough-in | 3/1/2016 | 3/2/2016 | 3/2/2016 7:46:29 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|