Inspections for the day of: Thursday, March 2, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02101 ELE-Aging Inspection3/2/20173/2/20173/3/2017 1:28:16 PM DONE
Work covered under house permit ELE12-03075.
ELE17-00116 Electrical Rough-In3/1/20173/2/20173/2/2017 1:37:01 PMPFAIL
Rough-In Wall Inspection
Contact Jon Novak Phone #: ###-#### Inspection requested via web by Cathy Duchek
300.4- 2 1/2" deep studs used. MC cable shall be protected from physical damage where passing thru a hole in a framing member where hole does not maintain 1 1/4" from framing surface.
300.4- MC cable shall not be secured within 1 1/4" surface of framing member.
ELE16-01667 Electrical Rough-In3/1/20173/2/20173/2/2017 10:53:25 AMAPASS
Town house 112 and 1st and 2nd floor lobby Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted walls and hardlids rough in ok cover
ELE16-03895 Rough-In Permanent Service3/2/20173/2/20173/2/2017 10:23:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder
Rough in ok cover p/s u/g n ok
ELE16-04077 Final3/1/20173/2/20173/2/2017 9:41:11 AMAFAIL
single story model, 1st one you come to. PLEASE INSPECT AS EARLY AS POSSIBLE. THANKS, ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn
210.52(D)- Powder bath shall have a receptacle outlet located on wall adjacent to and within 36" of outside edge of basin. Exterior not conplete due to wall finishes not done. Checked interior so house could be staged as a model house. OK to stage. Spoke with wireman on site.