BLD16-02870
| FIRE-Final Inspection | 3/2/2017 | 3/2/2017 | 3/2/2017 2:02:24 PM | P | FAIL |
|
|
Not ready for a final yet, I went over requirements with Chris such as needing the project related fire alarm permit addressed, remove the deadbolt on the beer cooler, need fire extinguisher for store, need verification of permiting through Fire Dept,, need verification Fire Dept is ok with the pumps/tanks and lack of 6" at the gas pumps, testing of the emergency off buttons, missing exit discharge lights....ect
|
FIR16-00647
| INSP-Alarm Testing | 3/1/2017 | 3/2/2017 | 3/2/2017 1:58:54 PM | P | FAIL |
|
|
No testing performed. Manual pull stations are mounted too high, strobe in cooler is overspaced, smoke detectors are mounted too low, no map, no knox box, no as-builts
|