Inspections for the day of: Friday, March 2, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02649 Electrical Rough-In3/2/20183/2/20183/2/2018 3:20:03 PMPPART
Contact is Andy Chambers - ceiling inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Grid for rooms noted on print, storage 148 and office 177. Also tested nurses station and bathroom 185, and patient rooms 3 thru 6 and 8 thru 11. All have receptacles with in 6' of a sink which fall under 210.8(B)(5) exception 2 to 5. Contractor to verify catagory 2 patient bed general care space with architect. Noted on contractor print as well.
ELE17-03991 Final3/1/20183/2/20183/2/2018 2:09:41 PMPPASS
garage code 1234 Phone #: ###-#### Inspection requested via web by Jay Hutchison Final ok
ELE18-00237 Final3/1/20183/2/20183/2/2018 2:09:12 PMPPASS
garage code 1234 Phone #: ###-#### Inspection requested via web by Jay Hutchison Final ok
ELE18-00792 Final3/1/20183/2/20183/2/2018 1:21:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Final ok
ELE18-00792 Electrical Rough-In3/2/20183/2/20183/2/2018 1:21:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Mini split rough in ok cover
ELE18-00313 Electrical Rough-In3/2/20183/2/20183/2/2018 1:11:42 PMPPART
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Solar panels on back order, stated same brand normally used. Discussed signage for 2 seperate solar disconnecting means, 1 near service and 1 at exterior of other garage. Micro inverters and rack system listing confirmed.
ELE18-00765 Temporary Service3/2/20183/2/20183/2/2018 12:36:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE17-04207 Final3/1/20183/2/20183/2/2018 11:31:42 AMAPASS
Phone #: ###-#### Inspection requested via web by cris flores
Final ok
ELE17-03546 Final3/1/20183/2/20183/2/2018 11:31:02 AMAPASS
Phone #: ###-#### Inspection requested via web by cris flores
Final ok
ELE18-00231 Electrical Rough-In3/1/20183/2/20183/2/2018 11:06:45 AMAPASS
FLOOR HEAT Inspection only, access 4878 Phone #: ###-#### Inspection requested via web by David Nelson
Master bath floor heat rough in ok cover
ELE18-00235 Final3/2/20183/2/20183/2/2018 10:55:35 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Patrick Paz Inspection cancelled from web by: Patrick Paz
ELE18-00603 Electrical Rough-In3/1/20183/2/20183/2/2018 10:47:21 AMAPASS
Contact is Jim Noll - wall rough-in inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Walls and seating area so grid can be painted. Few open boxes above this grid tha will be checked next trip. Rough in noted ok cover
ELE18-00413 Electrical Rough-In3/1/20183/2/20183/2/2018 10:45:48 AMAPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders only due to existing floor boxes said to be abandoned with several open knockouts in them. They are spread through out entire ceiling.
Boarders only rough in ok cover.
ELE17-04339 Final3/2/20183/2/20183/2/2018 9:27:44 AMPPASS
code 4224 . Ready now. Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE18-00765 Temporary Service3/1/20183/2/20183/2/2018 8:59:06 AMAFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk
110.27- Panel cover shall be in place to protect against accidental contact.
ELE18-00784 Rough-In Permanent Service3/1/20183/2/20183/2/2018 8:47:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok