Inspections for the day of: Wednesday, March 20, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-00755 Permanent Service3/19/20023/20/20023/20/2002 12:00:00 AMAPASS
dan- ###-#### for ped only ok

p/s u/g new ok 3/20/2002 12:38:53 PM
ELE02-00729 Electrical Rough-In3/19/20023/20/20023/20/2002 12:00:00 AMAPASS
r/i- chris ###-#### ok 3/20/2002 10:00:14 AM
ELE02-00757 Final3/19/20023/20/20023/20/2002 12:00:00 AMAPASS
ok 3/20/2002 10:56:38 AM
ELE02-00760 Rough-In Permanent Service3/20/20023/20/20023/20/2002 12:00:00 AMPPASS
###-#### MIKE CALL 1ST PLEASE
r/i ok
3/20/2002 4:46:06 PM
ELE02-00608 Electrical Rough-In3/20/20023/20/20023/20/2002 12:00:00 AMPFAIL
###-#### cor. posted called left message 300.4 protection for MC cable 11/4 3/20/2002 3:01:40 PM
ELE02-00159 Electrical Rough-In3/20/20023/20/20023/20/2002 12:00:00 AMPPART
CEILING INSPECT ON NORTH SIDE ALLISON ###-#### ok 3/20/2002 1:31:48 PM
ELE01-03195 Final3/20/20023/20/20023/20/2002 12:00:00 AMPPASS
fn insp- craig- ###-####- for access use gate & code is 1969 ok 3/20/2002 2:17:13 PM
ELE02-00767 Permanent Service3/20/20023/20/20023/20/2002 12:00:00 AMPPASS
###-#### call first to meet there

existing p/s u/g needs meter only set for house panel 3/20/2002 3:51:26 PM
ELE02-00747 Rough-In Permanent Service3/19/20023/20/20023/20/2002 12:00:00 AMPFAIL
###-#### bud called needs #4 copper for concrete encased electrode when not poured in footing 3/20/2002 2:40:52 PM