Inspections for the day of: Wednesday, March 20, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00006 FIRE-Final Inspection3/19/20023/20/20023/20/2002 12:00:00 AMAFAIL
provide 4" suite numbers, provide one fire extinguisher with current inspection tag mounted at 48" above finish floor, only one exit can have key locking hardware and that door must have sticker. The other door must have keyed hardware removed and approved door hardware provided, provide testing duct detector for tenant space, provide access to fire riser room so verification of monitoring and inspection tags 3/20/2002 10:38:22 AM
BLD02-00008 FIRE-Final Inspection3/19/20023/20/20023/20/2002 12:00:00 AMAFAIL
provide 4" suite numbers for tenant space, provide fire extinguisher, provide duct detector testing 3/20/2002 10:52:46 AM
FIR02-00041 INSP-Final Inspection3/19/20023/20/20023/20/2002 12:00:00 AMAPASS
fire sprinkler system finaled 3/20/2002 10:50:44 AM
BLD99-00444 FIRE-Final Inspection3/19/20023/20/20023/20/2002 12:00:00 AMPNR
Inspection was really a conference. Went over fire extinguisher locations, permanent address location, change out of door hardware to approved type 3/20/2002 4:28:24 PM