Inspections for the day of: Thursday, March 20, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00059 INSP-Final Inspection3/19/20033/20/20033/20/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/19/2003 at 9:48:48 AM. Contact: ###-####. sprinkler system requires annual inspection; duct detectors not installed in straight piece of duct; tested for troubles; alarms; sprinkler tampers and flow okay 3/20/2003 4:12:19 PM
FIR03-00016 INSP-Alarm Testing3/19/20033/20/20033/20/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/19/2003 at 11:30:48 AM. Contact: ###-####. duct detectors powered by panel; need calc's and it appears larger amp batteries will be needed; need to test sprinkler controls/flow 3/20/2003 10:37:28 AM
BLD02-02924 FIRE-Final Inspection3/19/20033/20/20033/20/2003 12:00:00 AMAFAIL
###-#### can do fire alarm inspection for Mountain Alarm at the same time awaiting alarm final; exit/emergency lights okay; need sprinkler canopy and test controls/flow with alarms 3/20/2003 10:38:42 AM
BLD02-03016 FIRE-Final Inspection3/19/20033/20/20033/20/2003 12:00:00 AMAPART
JEREMY; Phone #: ###-#### Internet Inspection Request from: Annette Moore per Dave Miller/Troy temp is approved pending fire alarm permit approval/testing; a new full height partition is installed creating new conference room which has overspaced sprinkler at 11 foot from new partition 3/20/2003 8:17:43 AM
FIR02-00385 INSP-Sprinkler Rough-in/Hydro3/19/20033/20/20033/20/2003 12:00:00 AMAPART
RUSS; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on all piping in pump room 3/20/2003 11:09:56 AM
BLD02-03101 FIRE-Final Inspection3/19/20033/20/20033/20/2003 12:00:00 AMAPART
###-#### - ok for temp. occ. only
BLD02-01533 FIRE-Final Inspection3/20/20033/20/20033/20/2003 12:00:00 AMAPART
temp occ approved pending standpipe interconnection; alarm tampers/flow of pump
BLD02-01413 FIRE-Final Inspection3/20/20033/20/20033/20/2003 12:00:00 AMPPART
temp occ aprroved per agreementletter to interconnect standpipes and monitor tampers in basement
FIR03-00110 INSP-Conference3/19/20033/20/20033/20/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 3/19/2003 at 4:57:26 PM. Contact: ###-####. partial stub out okay 3/20/2003 4:12:49 PM
FIR02-00473 INSP-Sprinkler Rough-in/Hydro3/20/20033/20/20033/20/2003 12:00:00 AMPPART
TERRY; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro on overhead okay 3/20/2003 4:13:14 PM
BLD03-00260 FIRE-Final Inspection3/20/20033/20/20033/20/2003 12:00:00 AMPPASS
CARLA ###-#### FOR BEAUTY all items from previous inspection corrected 3/20/2003 4:33:26 PM