FIR06-00154
| INSP-Final Inspection | 3/20/2006 | 3/20/2006 | 3/20/2006 3:56:10 PM | P | PASS |
|
|
Items on correction notice have been completed, permit finaled.
|
BLD04-02772
| FIRE-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 3:47:07 PM | A | PASS |
|
|
Fire life safety is satisfactory, project related fire sprinkler and fire alarm permits have been finaled.
|
FIR06-00073
| INSP-Supply line flush | 3/17/2006 | 3/20/2006 | 3/20/2006 3:43:55 PM | P | FAIL |
|
|
Inspection was for UG supply line cover. Depth of bury for the entire pipe run does not meet the required 4'-6" to top of pipe for this locality (the actual install is approximately 3'-6" from top of pipe to floor slab at the building and 3'-6" to 4'-0" to grade for the remainder).
|
FIR05-00372
| INSP-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 2:39:23 PM | A | FAIL |
|
|
Some items on previous correction notice dated 11/10/05 have not been completed including the missing escutcheon at the womens restroom lobby area, missing coverage at the roof hatch. Two heads in the east projection room are spaced incorrectly for min. spacing, no access to storage room next to managers office for OH spacing verification. Plans have been resubmitted for OH spacing at the projection rooms, however an alternate agreement for "no storage allowed" has been accepted in lieu of sprinkler modifications.
|
BLD05-02886
| FIRE-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 11:32:56 AM | A | FAIL |
|
|
See on site c/n for list of defficiencies including door hardware, max occupant load sign, hood and sprinkler permit issues.
|
BLD05-01998
| FIRE-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 11:30:59 AM | A | FAIL |
|
|
The project related hood and sprinkler permits must be finaled prior to life safety final, storage shelves that extend underneath the cooking hood canopy must be removed, provide max occupant load sign for the dining area, remove keyed locking hardware at the NE door, provide signage at the door to be used as the main entry/exit.
|
BLD06-00035
| FIRE-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 10:28:27 AM | A | PASS |
|
|
Items on correction notice have been completed, life safety passed.
|
FIR06-00114
| INSP-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 10:26:55 AM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR06-00080
| INSP-Final Inspection | 3/17/2006 | 3/20/2006 | 3/20/2006 10:25:43 AM | A | PASS |
|
|
Fire sprinkler work is satisfactory, inspection passed.
|